SECTION 8 – TROUBLESHOOTING
INSUFFICIENT VACUUM LEVELS
Causes of insufficient vacuum level of purging line and
countermeasures against them.
TABLE 47 -
INSUFFICIENT VACUUM LEVELS
ITEM
CAUSE
COUNTERMEASURE
1
Purge pump trouble
Contact your local Johnson Controls Service Office.
2
Deterioration of vacuum pump oil
Replace the vacuum pump oil.
3
Wrong operation of purging line switching when
vacuum pump capacity was checked
. Confirm the valves
are open or closed.
4
Deterioration of vacuum pump belt
Contact your local Johnson Controls Service Office.
5
Leakage in purge pipe line
6
Blocked or dysfunctional purge solenoids
7
Check valve does not open
8
Valve V21 mistakenly open
. Confirm the valves
are open or closed.
ACTIONS TO TAKE AGAINST POWER
FAILURE
If the main power fails, follow the steps in the flow-
chart shown
Содержание YHAU-CL Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 47: ...JOHNSON CONTROLS 47 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 128: ...JOHNSON CONTROLS 128 FORM 155 30 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...