SECTION 4 - TECHNICAL DATA
This section includes technical information
about the unit, such as weight, dimensions, and
electrical data.
The numbers shown in
are the
allowable ranges for each parameter. Not all combi-
nations are possible. Please check with your Johnson
Controls Service Center to see if your temperature dif-
ferential is possible.
TABLE 7 -
TYPICAL OPERATIONAL RANGE
PARAMETER
ALLOWABLE RANGES
EUROPE
FOR OTHER
COUNTRIES
OPTIONAL
Chilled Water In
44.6 - 77 °F
39.2 - 44.6 °F
Chilled Water Out
39.2 - 60.8 °F
33.8 - 39.2 °F
Cooling Water In
68 - 98.6 °F
Cooling Water Out
77 - 107.6 °F
CL
Hot Water In
158 - 230 °F
158 - 210.2 °F
Hot Water Out
140 - 228.2 °F
140 - 208.4 °F
CH
Hot Water In
231.8 - 320 °F
212 - 320 °F
Hot Water Out
176 - 302 °F
176 - 302 °F