FORM 150.44-NM4
75
YORK INTERNATIONAL
3. If discharge pressure of either system reaches 340
PSIG, the reversing fan will be turned off. At the
same time, fan 2 (6M) will energize. This fan will
remain on until discharge pressure of either sys-
tem drops below 120 PSIG.
4. If discharge pressure of either system reaches 360
PSIG and compressor run time has exceeded 30
seconds, fan 1 (5M) will energize turning the fan in
the forward direction. This fan will remain on until
discharge pressure of either system drops to 140
PSIG.
Table 2 shows the operation of both modes of fan con-
trol previously discussed.
HOT GAS BYPASS (LOADMINDER) OPTION
General
The Hot Gas Bypass Option is available as a factory
installed option to prevent compressor cycling and water
temperature fluctuation at low load. This is ac-
complished by providing further capacity reduction be-
low the last step of compressor cylinder unloading by
introducing an artificial load to the cooler, which keeps
the compressor on the line. The option will provide hot
gas bypass on both compressors enabling hot gas to
be active regardless of which compressor is in the lead.
NOTE: The microprocessor will only activate the hot
gas on the lead compressor.
The hot gas bypass consists of a pilot operated regu-
lating valve with an integral solenoid. The pilot operated
solenoid is controlled by the microprocessor according
to water temperature. The regulating valve which be-
comes activated when the solenoid is energized, is con-
trolled by suction pressure to modulate the flow of gas
in a bypass connected from the compressor discharge
to the cooler inlet. The following text will explain how the
hot gas solenoid is activated by the microprocessor in
both return and in leaving water control.
LWT Control Hot Gas Operation
The hot gas solenoid is energized when the leaving
water temperature falls below the Target water tem-
perature, if the compressor is on its minimum stage of
loading. Hot gas may then be fed according to the suc-
tion pressure and the pressure regulating valve set-
ting. Once activated, the micro will keep the solenoid
energized until the leaving water temperature rises
above the high limit of the Control Range or until the
load becomes so low that the hot gas can no longer
keep temperature within the control range and the mi-
cro turns the compressor off. Details for setting the pres-
sure regulator follow.
TABLE 2
LOW AMBIENT FAN CYCLING
NOTE
:
A fan with a reversing contactor will have the reversing contactor mechanically locked out when Fan 1 is running forward. The forward
contactor will also be locked out when the Fan 1 is running in reverse.
CONTROL BY
CONTROL BY
TEMPERATURE & PRESSURE
PRESSURE ONLY
FAN
CONT.
BELOW 25°F PRESSURE
ABOVE 25°F TEMP.
TEMPERATURE
CONTROL ONLY
CONTROL ONLY
HAS NO EFFECT
ON
OFF
ON
OFF
ON
OFF
Either System
Either System
1 REV
7M
Discharge
Discharge
Will Not Start
35°F or
Press. Exceeds
Press. Drops
Above 25°F
340 PSIG
320 PSIG
120 PSIG
320 PSIG
Below 120 PSIG
Turns OFF Only
Either System
Either System
if Discharge
2
6M
Discharge
Discharge
25°F
Pressure of
340 PSIG
120 PSIG
Press. Exceeds
Press. Drops
Either
340 PSIG
Below 120 PSIG
System Drops
Below 120 PSIG
Either System
Either System
1 FWD
5M
Discharge
Discharge
45°F
40°F
360 PSIG
140 PSIG
Press. Exceeds
Press. Drop
360 PSIG
Below 140 PSIG
Содержание YCAZ33BA3
Страница 18: ...YORK INTERNATIONAL 18 LD01992 LD01993 LD01994 FIG 6 SYSTEM WIRING CONNECTION DIAGRAM SYSTEM WIRING YCA 50 90...
Страница 19: ...FORM 150 44 NM4 19 YORK INTERNATIONAL FIG 6 SYSTEM WIRING Cont d...
Страница 21: ...FORM 150 44 NM4 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD01997 LD01998 LD01999...
Страница 87: ...FORM 150 44 NM4 87 YORK INTERNATIONAL...