FORM 150.44-NM4
51
YORK INTERNATIONAL
Oil Pressure Safety
The Oil Pressure Safety assures that the compressors
mechanical components receive proper lubrication. The
micro begins monitoring compressor oil pressure after
4 seconds of operation. For operating periods of 4 sec-
onds to 30 seconds, oil pressure must be greater than
5 PSID. From 30 seconds to 240 seconds, oil pressure
must be greater than 20 PSID. After 240 seconds, oil
pressure must be greater than 25 PSID for as long as
the compressor continues to run. If the required oil pres-
sure limits are not met, the system will shut down.
The micro computes differential oil pressure by meas-
uring oil pump pressure and subtracting suction pres-
sure (Oil - Suction = Oil PSID).
An example of an oil pressure fault display message is
shown below.
Discharge Pressure Safety
The Discharge Pressure Safety assures that the sys-
tem pressure does not exceed safe working limits which
could open a relief valve or other pressure relief de-
vice causing refrigerant loss.
This safety is a back-up for the mechanical safety in
the system. Anytime the cut-out point is exceeded, the
system will shut down.
The Discharge Pressure Safety Cut-out is programma-
ble by the user (Page 34). An example of a discharge
pressure fault display message is shown below.
NOTE: This safety is only operable if optional dis-
charge pressure transducers are installed.
Pumpdown Safety
The Pumpdown Safety assures that a compressor does
not run unless it completes a proper pumpdown. This
prevents operation of a refrigerant system which has a
leaking liquid line solenoid valve.
On start-up, the system must pump down to the suc-
tion pressure cut-out within 300 seconds or the system
will shut down.
An example of the Pump down fault display message
is shown below.
NOTE: LLSV refers to liquid line solenoid valve.
Motor Protector
Three internal temperature sensors are built into the
motor stator. These sensors are wired into the motor
protector module located inside the Motor terminal box.
As the motor windings heat and cool, the resistance of
the motor temperature sensors will change. If the wind-
ings overheat, the change in resistance in the sensors
will be sensed by the Motor protector module. The mod-
ule will open its MP contacts breaking the 115VAC fed
to the motor contactor. When the motor contactor
de-energizes, motor current falls to zero. The low mo-
tor current is sensed by the microprocessor and the
system is shut down. For more information, see MO-
TOR CURRENT SAFETY (Page 50).
Auto-restart will be permitted after a shutdown, when
the motor sensors cool and the MP contacts close. A
fault lock-out will result if safety thresholds are exceeded
three times in a 90 minute period.
Mechanical High Pressure Cut-Out (HPCO)
A mechanical high pressure cut-out is located on each
compressor discharge or in the compressor head. This
is the primary high pressure safety in the system. Any
microprocessor controls are secondary.
Anytime discharge pressure exceeds 405 PSIG, the
contacts in the high pressure cut-out will open which
removes 115VAC from the motor protector module.
When 115VAC control power is lost to the module, the
modules MP contacts open breaking the 115 VAC fed
to the motor contactor. The motor contactor de-ener-
gizes and motor current falls to zero. The low motor
current is sensed by the microprocessor and the sys-
tem is shut down. For more information see MOTOR
CURRENT SAFETY (Page 50).
Auto-restart will be permitted after a shutdown when
discharge pressure drops to below 330 PSIG which
allows the mechanical high pressure cut-out to reset
and its contacts to close. This re-applies 115VAC to
the motor protector closing the MP contact. A fault
lock-out will result if safety thresholds are exceeded
three times in a 90 minute period.
S Y S # 1
L O W
S U C T I O N
S Y S # 2
L O W
S U C T I O N
S Y S # 1
L O W
O I L
P R E S S
S Y S # 2
L O W
O I L
P R E S S
S Y S # 1
H I G H
D S C H
S Y S # 2
H I G H
D S C H
S Y S # 1
L L S V
N O T
O N
S Y S # 2
L L S V
N O T
O N
Содержание YCAZ33BA3
Страница 18: ...YORK INTERNATIONAL 18 LD01992 LD01993 LD01994 FIG 6 SYSTEM WIRING CONNECTION DIAGRAM SYSTEM WIRING YCA 50 90...
Страница 19: ...FORM 150 44 NM4 19 YORK INTERNATIONAL FIG 6 SYSTEM WIRING Cont d...
Страница 21: ...FORM 150 44 NM4 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD01997 LD01998 LD01999...
Страница 87: ...FORM 150 44 NM4 87 YORK INTERNATIONAL...