
FORM 150.44-NM4
7
YORK INTERNATIONAL
OPERATIONAL LIMITATIONS
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and op-
eration beyond these limits may cause serious dam-
age to the compressor.
VOLTAGES
TEMPERATURES AND FLOWS
MODEL
LVG. WATER
COOLER
AIR ON
YCA
TEMP. °F
GPM
COND. - °F
MIN.
1
MAX.
MIN.
MAX.
MIN.
2
MAX.
3
Z33BA3
40
50
75
250
0
130
Z44BA3
40
50
90
250
0
130
Z74BB3
40
50
90
250
0
130
Z77CB3
40
50
90
315
0
130
Z88DB3
40
50
130
390
0
130
NOTES
:
1. Units can be used for brine temperatures between 15°F and 39°F
by resetting standard controls.
2. Operation below 25°F requires the Optional Low Ambient Kit
(Minimum recommended operating temperature is 0°F).
3. Operation above 115°F requires Optional High Ambient Kit (Maxi-
mum recommended operating temperature is 130°F).
4. The evaporator is protected against freeze-up to 20°F with an
electrical heater cable standard.
CAUTION: Excessive flow will cause damage to the
cooler. Do not exceed maximum Cooler
GPM. Special care should be taken when
multiple chillers are fed by a single
pump.
LD01981
CODE
MODEL YCA
B
Z33BA3
C
Z44BA3, Z74BB3, Z77CB3
D
Z88DB3
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
380-3-60
355
415
460-3-60
414
506
380/415-3-50
342
440
346-3-50
311
381
575-3-60
517
633
Содержание YCAZ33BA3
Страница 18: ...YORK INTERNATIONAL 18 LD01992 LD01993 LD01994 FIG 6 SYSTEM WIRING CONNECTION DIAGRAM SYSTEM WIRING YCA 50 90...
Страница 19: ...FORM 150 44 NM4 19 YORK INTERNATIONAL FIG 6 SYSTEM WIRING Cont d...
Страница 21: ...FORM 150 44 NM4 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD01997 LD01998 LD01999...
Страница 87: ...FORM 150 44 NM4 87 YORK INTERNATIONAL...