YORK INTERNATIONAL
54
PRINT KEYS
26572A
PRINT
KEYS
GENERAL
The PRINT keys allow the operator to obtain a remote
print-out of real-time system operating data and a print-
out of system data at the instant of the fault on the
last three faults which occurred on the chiller.
If a remote printer is not being used, or the desire is to
obtain data locally at the panel, the same keys allow ac-
cess to identical fault data. Identical and additional
real-time information is available by using a combination
of the PRINT keys and the other keys on the keypad.
An explanation of the use of the keys for remote printer
or local data retrieval will follow. An optional printer
(Page 76) will be required for remote printout.
REMOTE PRINTOUT
Oper Data
The OPER DATA key allows the operator to remotely
obtain a printout of current system operating parame-
ters. When the key is pressed, a snapshot will be taken
of system operating conditions and panel programming
selections. This data will be temporarily stored in mem-
ory and transmission of this data will begin to the re-
mote printer. As the data is transmitted, it will be erased
from memory.
A sample printout is shown in Fig. 19.
History
The HISTORY key allows the operator to remotely
obtain a printout of information relating to the last 3
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 4/17/91
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI -RECYCYLE TIMER 119 SEC
RETURN WATER TEMP
65.1 DEGF
LEAVING WATER TEMP
54.0 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
45.0 DEGF
OUTSIDE AIR TEMP
75.0 DEGF
LOW AMBIENT CUTOUT
10.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
50 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
143 PSIG
OIL PRESSURE
75
PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
8 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
80 PSIG
OIL PRESSURE
1
PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
S M T W T F S
* = HOLIDAY
SUN
START=00:00AM
STOP=00:00AM
MON
START=00:00AM
STOP=00:00AM
TUE
START=00:00AM
STOP=00:00AM
WED
START=00:00AM
STOP=00:00AM
THU
START=00:00AM
STOP=00:00AM
FRI
START=00:00AM
STOP=00:00AM
SAT
START=00:00AM
STOP=00:00AM
HOL
START=00:00AM
STOP=00:00AM
OPER
DATA
FIG. 19
OPERATING DATA PRINTOUT
HISTORY
Содержание YCAZ33BA3
Страница 18: ...YORK INTERNATIONAL 18 LD01992 LD01993 LD01994 FIG 6 SYSTEM WIRING CONNECTION DIAGRAM SYSTEM WIRING YCA 50 90...
Страница 19: ...FORM 150 44 NM4 19 YORK INTERNATIONAL FIG 6 SYSTEM WIRING Cont d...
Страница 21: ...FORM 150 44 NM4 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD01997 LD01998 LD01999...
Страница 87: ...FORM 150 44 NM4 87 YORK INTERNATIONAL...