86
YORK INTERNATIONAL
BAS INTERFACE OPTION
(REMOTE RESET OPTION)
The Remote Reset Option allows resetting of the water
temperature setpoint using a 0 - 10VDC input, a 4-20mA
input, or a dry contact. The electronic circuitry in the
option converts the signals mentioned, above into pulse
width modulated (PWM) signals which the microproces-
sor can understand. Whenever an offset is called for, the
change may be noted by the user by pressing the RE-
MOTE RESET TEMP/RANGE Key on the Keypad. All
refresh requirements normally associated with PWM in-
puts will be automatically taken care of by the electron-
ics in the option.
It is important to note that the maximum offset, when this
option is installed, is 20°F. This is due to the electronics
limitation of maximum 11 sec. pulse. If a greater than
20°F offset is required, a user supplied PWM signal of up
to 21 sec. is needed and the Remote Reset Option can-
not be installed.
The Remote Reset Option P/N 471-01232-181 consists
of a Remote Reset printed circuit board, a mounting
bracket and associated wiring. Each of the 3 signal
types will require individual jumpering of the printed cir-
cuit board. This will be discussed in the following text.
0 - 10VDC
Jumpers JU2 and JU4 must be IN. All other jumpers
should be OUT. Program the REMOTE TEMP SET-
POINT RANGE (page 65) for 40°F which will allow a 20°F
offset with an input of 10VDC. The temperature will be
offset linearly according to the voltage (0 - 10VDC) ap-
plied.
The 0 - 10VDC signal should be connected to the + and
- terminals on the TB3 Terminal Block at the right of the
Microprocessor Board. Be sure polarity is correct.
CAUTION: THE 0-10VDC INPUT SIGNAL WIRING
MUST NOT BE EARTH GROUNDED!
4-20mA
Jumpers JU3 and JU5 must be IN. All other jumpers
should be OUT. Program the REMOTE TEMP SET-
POINT RANGE (page 65) for 40°F which will allow a 20°F
offset with an input of 20mA. There will be no offset with
an input of 4mA. The temperature will be offset linearly
according to the current (4-20mA) applied.
The 4-20mA input signal should be connected to the +
and - terminals on the TB3 Terminal Block at the right of
the microprocessor board. Be sure polarity is correct.
CAUTION: THE 4-20mA INPUT SIGNAL WIRING
MUST NOT BE EARTH GROUNDED!
Dry Contact
A dry contact may also be used to offset temperature.
This allows a single offset whenever the contact is
closed. The offset is determined by the adjustment of the
R11 potentiometer on the Remote Reset Board. Adjust
the potentiometer as needed to obtain the desired offset.
Jumper JU1 must be IN. All other jumpers must be OUT.
Program the REMOTE RESET TEMP SETPOINT
RANGE (page 65) for 40°F which will allow the R11 pot to
be adjusted for an offset of as much as 20°F when the
contact is closed.
The dry contact should be connected directly to the P1-1
and P1-2 terminals on the Remote Reset Board (Fig. 40).
NOTE: The coil of the controls used for reset must be
suppressed. Use YORK P/N 031-00808-000
suppressor.
The Remote Setpoint Reset will not operate
when a Remote Control Center Option is con-
nected to the micropanel. The Remote Control
Center will always determine the setpoint.
FIG. 40
REMOTE RESET BOARD
LD02190
Содержание YCAJ44HE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...