FORM 150.60-NM3
75
YORK INTERNATIONAL
FIG. 30
CONDENSER WATER PUMP CONTACT
CONNECTION POINT
LD02178
This option utilizes a second Relay Output Board and
associated wiring. The part number for the Field Mounted
Pump Control Kit is 471-01232-101. This kit is not re-
quired if a second Relay Output Board is already in-
stalled.
NOTE: Any inductive devices (contactor/relay coil) con-
nected to these contacts must be suppressed
with YORK PAN 031-00808 supplied by others.
Otherwise, nuisance faults may occur.
0°F LOW AMBIENT OPTION
The standard chiller is designed to operate in an ambient
of 25°F or higher. If it is necessary to operate the chiller
in an ambient between 0° and 25°F, the chiller should be
purchased with the factory installed Low Ambient Op-
tion.
NOTE: Occasional operation below 0°F is normally pos-
sible. In these cases a low suction pressure
shutdown may sometimes occur, but can usu-
ally be tolerated.
Operation
The fundamental purpose of the Low Ambient Option is
to reduce the capacity of the condenser when the am-
bient temperature is in the 0 to 25°F range. This assures
that adequate discharge pressures can be maintained at
low temperatures which will eliminate low suction pres-
sure faults.
LOW AMBIENT KIT
MODEL NUMBER
PART NUMBER
FIELD MOUNTED
YCAZ88EE8-17P
471-01262-102
YCAZ88EE8-28P
471-01262-102
YCAZ88EE8-46P
471-01262-102
YCAZ88EE8-58P
471-01262-102
YCAJ44HE8-17P
471-01262-102
YCAJ44HE8-28P
471-01262-102
YCAJ44HE8-46P
471-01262-102
YCAJ44HE8-58P
471-01262-102
YCAJ54HE8-17P
471-01262-102
YCAJ54HE8-28P
471-01262-102
YCAJ54HE8-46P
471-01262-102
YCAJ54HE8-58P
471-01262-102
YCAJ55HE8-17P
471-01262-101
YCAJ55HE8-28P
471-01262-101
YCAJ55HE8-46P
471-01262-102
YCAJ55HE8-58P
471-01262-102
YCAJ65HE8-17P
471-01262-101
YCAJ65HE8-28P
471-01262-101
YCAJ65HE8-46P
471-01262-102
YCAJ65HE8-58P
471-01262-102
Operation at low ambients is accomplished by cycling
fans according to discharge pressure. This requires the
addition of discharge pressure transducers which allows
the microprocessor to add two additional steps of control
to the standard fan control scheme. Fans are now al-
lowed to cycle completely off and two fans on each sys-
tem are permitted to run in the reverse direction. This
reduces the capacity of the condenser as required. Re-
verse rotation of the fans is accomplished by the addition
of reversing contactors.
Components
The Low Ambient Option consists of 3 kits; a Low Ambi-
ent Kit for the appropriate chiller from the list below, a
471-01262-111 Discharge Pressure Readout Kit, and
also a 471-01232-101 Relay Board Kit. All three kits are
required. The Relay Board Kit is not required if two Relay
Boards are already present in the panel.
When the Low Ambient Option is installed, the following
physical changes are made to the standard chiller:
1. Discharge pressure transducers and wiring are
added.
2. Reversing contactors 7M and 10M with supporting
wiring are added.
3. A second Relay Output Board and wiring is in-
stalled.
Содержание YCAJ44HE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...