NOTES for Electrical Data pages 34 - 39:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit, per N.E.C Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system
#1 MCA values in the YCA Tables: -17, add 10 amps; -28, add 9 amps; -46, add 4 amps; -58, add 3 amps.
2. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1). It is not
recommended in applications where brown-outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in
excess of 95°F is anticipated.
3. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C.440-22.
4. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit,
per N.E.C.440-12A1.
5. Maximum HACR is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per U.L. 1995
Fig. 36.2.
6. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), (3) or (4)
indicated the number of termination points which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the
National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compr system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - #2/0 (50 - 90 Tons) or #6 - 350 MCM (95 - 230 Tons).
ELECTRICAL DATA
DUAL COMPRESSOR POWER SUPPLY WIRING (STANDARD)
SYSTEM #1 WIRING
SYSTEM #2 WIRING
MODEL
MAX.
MAX SIZE
INCOMING
COND
MAX.
MAX SIZE
INCOMING
COND
YCA
MCA
1
DUAL ELEM DIS. CKT. BKR.
WIRE RANGE
6
CPR CPR
FAN MCA
1
DUAL ELEM DIS.
CKT. BKR.
WIRE RANGE
6
CPR CPR
FAN
FUSE
MIN.
4
HACR
5
(CU ONLY)
RLA LRA
FLA
FUSE
MIN.
4
HACR
5
(CU ONLY)
RLA LRA
FLA
MIN.
2
MAX.
3
TYPE
EACH
MIN.
2
MAX.
3
TYPE
EACH
Z88EE8 -17
291
350
350
400
450
(2)#4-250MCM
207 858
16
291
350
450
400
450
(2)#4-250MCM 207 858
16
Z88EE8 -28
258
350
400
400
400
(2)#4-250MCM
180 746
16.4
258
350
400
400
400
(2)#4-250MCM 180 746
16.4
Z88EE8 -46
129
175
200
200
200
(2)#4-250MCM
90 373
8.1
129
175
200
200
200
(2)#4-250MCM
90 373
8.1
Z88EE8 -58
102
125
150
100
150
(2)#4-250MCM
72 304
5.9
102
150
150
100
150
(2)#4-250MCM
72 304
5.9
J44HE8 -17
320
400
500
400
500
(2)#4-250MCM
230 731
16
320
400
500
400
500
(2)#4-250MCM 230 731
16
J44HE8 -28
283
350
450
400
450
(2)#4-250MCM
200 636
16.4
283
350
450
400
450
(2)#4-250MCM 200 636
16.4
J44HE8 -46
142
175
225
200
225
(2)#4-250MCM
100 318
8.1
142
175
225
200
225
(2)#4-250MCM 100 318
8.1
J44HE8 -58
112
150
175
200
175
(2)#4-250MCM
80 254
5.9
112
150
175
200
175
(2)#4-250MCM
80 254
5.9
J54HE8 -17
365
450
600
400
600
(2)1/0-500MCM 266 950
16
320
400
500
400
500
(2)#4-250MCM 230 731
16
J54HE8 -28
322
400
500
400
500
(2)#4-250MCM
231 826
16.4
283
350
450
400
450
(2)#4-250MCM 200 636
16.4
J54HE8 -46
162
200
250
200
250
(2)#4-250MCM
116 413
8.1
142
175
225
200
225
(2)#4-250MCM 100 318
8.1
J54HE8 -58
127
150
200
200
200
(2)#4-250MCM
92 330
5.9
112
150
175
200
175
(2)#4-250MCM
80 254
5.9
J55HE8 -17
365
450
600
400
600
(2)1/0-500MCM 266 950
16
365
450
600
400
600
(2)#4-250MCM 266 950
16
J55HE8 -28
322
400
500
400
500
(2)#4-250MCM
231 826
16.4
322
400
500
400
500
(2)#4-250MCM 231 826
16.4
J55HE8 -46
162
200
250
200
250
(2)#4-250MCM
116 413
8.1
162
200
250
200
250
(2)#4-250MCM 116 413
8.1
J55HE8 -58
127
150
200
200
200
(2)#4-250MCM
92 330
5.9
127
150
200
200
200
(2)#4-250MCM
92 330
5.9
J65HE8 -17
424
500
700
400
700
(2)1/0-500MCM 313 1101
16
365
450
600
400
600
(2)#4-250MCM 266 950
16
J65HE8 -28
373
450
600
400
600
(2)1/0-500MCM 272 976
16.4
322
400
500
400
500
(2)#4-250MCM 231 826
16.4
J65HE8 -46
187
225
300
200
300
(2)#4-250MCM
136 488
8.1
162
200
250
200
250
(2)#4-250MCM 116 413
8.1
J65HE8 -58
148
175
250
200
250
(2)#4-250MCM
109 390
5.9
127
150
200
200
200
(2)#4-250MCM
92 330
5.9
Содержание YCAJ44HE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...