FORM 150.60-NM3
41
YORK INTERNATIONAL
GENERAL
After Return or Leaving Chilled Liquid Control is selected
according to the users application and Switch #4 of Dip
Switch S1 on the Micro Board is properly configured to
select Return or Leaving control, the chilled liquid setpoints
can then be programmed into the control panel. Switch
#4 of S1 must be properly programmed or an incorrect
display message will appear when the CHILLED LIQUID
TEMP/RANGE key is pressed.
SEE “SELECTION OF
RETURN OR LEAVING CHILLED LIQUID CONTROL”
Page 40 if needed.
If remote temperature setpoint is being utilized, the RE-
MOTE RESET TEMP RANGE must be programmed. The
following information will cover programming both return
and leaving control. Refer to either the RETURN or LEAV-
NOTE: In LWT CONTROL, water temperature may un-
desirably rise when a compressor cycles off and
cannot restart because the anti-recycle timer is
still timing out. The effects can be reduced by
programming the anti-recycle timer (Page 36) for
a minimum of 300 seconds if it isn’t already pro-
grammed for 300 seconds. If problems still arise,
switch to RWT CONTROL.
Once the dip switch #4 on the Microprocessor Board is
properly positioned, the user will be able to view the ap-
propriate display when the CHILLED LIQUID TEMP/
RANGE is pressed. This display will show one of the
following messages depending upon S1 positioning:
R E T U R N
W A T E R
T E M P
C O N T R O L
L E A V I N G
W A T E R
T E M P
C O N T R O L
SETPOINTS KEYS
PROGRAMMING CHILLED LIQUID SETPOINTS
& REMOTE RESET TEMP RANGE
26572A(D)
ING WATER CONTROL section as required below. Pro-
gramming the REMOTE RESET TEMP RANGE is dis-
cussed later in this manual on Page 65.
PROGRAMMING RETURN WATER CONTROL
Chilled Liquid
Temp/Range
When the CHILLED LIQUID TEMP/RANGE key is
pressed, the following message will be displayed for 3
seconds indicating Dip Switch S1, Switch #4 on the Mi-
croprocessor Board is programmed properly:
R E T U R N
W A T E R
T E M P
C O N T R O L
CHILLED LIQUID
TEMP/RANGE
Содержание YCAJ44HE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...