FORM 150.60-NM3
81
YORK INTERNATIONAL
FIG. 34
ASSEMBLY AND WIRING
Installation Limitations
The following limitations must be adhered to. Failure to
do so may result in improper printer and/or chiller op-
eration.
1. The printer option is adaptable to all versions and
revisions of Microprocessor boards and EPROMs.
No modifications are necessary to the panel.
2. Maximum cable length between the printer and the
Microprocessor Board is 25 feet. Twisted pair
shielded cable is required.
3. The printer must be supplied a 115VAC source.
4. The printer may be left connected to the micro panel.
Parts
The following parts are required:
1. Weigh-Tronix IMP-24, Model 2600 printer.
2. 2.25" wide desk top calculator paper.
3. 25 ft. Twisted Pair Shielded Cable (minimum 3 con-
ductor), #18 AWG Stranded, 300V min. insulation.
4. (1 ea.) 25-pin Cannon connector and shell. Connec-
tor: Cannon P/N DB-25P or equivalent. Shell: Can-
non P/N DB-C2-J9.
Assembly and Wiring
All components should be assembled and wired as fol-
lows in Fig. 34. Strip the outside insulation back several
inches and individual wires about 3/8" to connect the
cable at the Micro Logic Board. Connect the shield of the
cable as shown on the Micro Logic Board. Do not con-
nect at the printer end of the cable.
WIRING
ASSEMBLY
LD02186
Содержание YCAJ44HE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...