FORM 150.60-NM3
63
YORK INTERNATIONAL
When AUTO Lead/Lag is utilized, the micro determines
which compressor is assigned to the lead and the lag.
A new lead/lag assignment is made whenever both com-
pressors shut down. The micro will assign the lead to
the compressor with the shortest anti-recycle time. This
will tend to balance run time between the two compres-
sors.
AUTO Lead/Lag will cause the lag compressor to auto-
matically become the lead, anytime the compressor cur-
rently in the lead shuts down due to a safety threshold
being exceeded. This is done to maintain water tempera-
ture as close to setpoint as possible. Additionally, the
lag system will automatically become the lead anytime
the system switch on the Microprocessor Board of the
compressor currently in the lead is placed in the OFF
position. This is also done to maintain water temperature
as close to setpoint as possible.
If MANUAL Lead/Lag is selected, an external dry con-
tact (switch) must be wired into the chiller. This contact
is supplied by others. When the contact is closed, SYS
2 will be the lead system. With the contact open, SYS 1
is the lead.
MICROPROCESSOR
BOARD
SYSTEM SWITCHES 1-4
ON MICROPROCESSOR BOARD
Manual Lead/Lag selection can be automatically over-
ridden by the micro to allow the lag compressor to auto-
matically become the lead, anytime the selected lead
compressor shuts down due to a safety threshold being
FIG. 22
LOCATION OF THE MICROPROCESSOR BOARD
26000A
26001A
FIG. 23
ALARM CONTACT CONNECTION
LOCATION
LD02178
Содержание YCAJ44HE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172...