YORK INTERNATIONAL
85
FORM 150.40-NM25
SINGLE CIRCUIT UNITS
ANNUNCIATION ALARM
An optional Annunciation Alarm Kit p/n 025-28396-101
can be supplied which contains a second relay output
board whose dry contacts will transition to function as a
warning if a fault (“F” Code on displays) occurs or power
is lost to the control panel. The system has a set of dry
contacts which are normally open (N.O.) and close when
control power is applied to the panel. Anytime control
power is lost or a fault occurs, the contact will open,
0°F LOW AMBIENT ACCESSORY
GENERAL
The standard chiller is designed to operate in an ambi-
ent temperature of 35°F (1.7°C) or higher. If it is neces-
sary to operate the chiller in an ambient between 0°F
(–17.8°C) and 35°F (1.7°C), the chiller should be pur-
chased with the factory installed Low Ambient Kit.
OPERATION
The fundamental purpose of the Low Ambient Kit is to
reduce the capacity of the condenser when the ambient
temperature is in the 0°F to 35°F range. This assures
that adequate discharge pressures can be maintained
at low temperatures eliminating low suction pressure
faults. This is accomplished in three ways as follows:
1. The normally open solenoid valve in the condenser
liquid line is energized to stop flow in one half of the
condenser, that is, one “V” bank in the condenser.
NOTE: The valve has an orifice which has been sized
to prevent liquid build-up in the inactive portion of the
condenser.
2. Louvered panels are installed to reduce flow of air
over the inactive side of the condenser to aid in pre-
venting liquid build-up.
3. Below 45°F (7.2°C) fans are cycled by discharge pres-
sure only.
COMPONENTS
When the Low Ambient Kit is installed, the following
physical changes are made to the standard chiller:
1. One normally open solenoid valve is added to the
condenser circuit liquid line.
FIG. 60 – ANNUNCIATION ALARM WIRING
breaking the alarm circuit. A 28VDC or 120VAC exter-
nal alarm circuit (by others) must be wired into the YORK
supplied alarm contact. If the alarm circuit is applied to
chillers used for critical duty (such as process duty, or
cooling other critical equipment) and the alarm circuit
should fail to function, YORK will not be liable for dam-
ages.
The kit contains a N.C. Contact wired into TB4 termi-
nals 300 and 301 (See Fig. 60).
00019TG(R)
ALARM IS WIRED TO TB5
300
&
301
FROM DRY CONTACTS (OPEN ON ALARM)
CONTACT RATING 28VDC, 120VAC
AT 1A. A SURGE PROTECTOR
(SUPPRESSOR) YORK P/N 031-00808
MUST BE WIRED IN PARALLEL WITH AN
INDUCTIVE ALARM DEVICE (I.E. RELAY
COIL) AND MUST BE PHYSICALLY
LOCATED AT THE COIL.
Содержание YCAG18
Страница 11: ...YORK INTERNATIONAL 11 FORM 150 40 NM25 SINGLE CIRCUIT UNITS LD01712 ELEMENTARY DIAGRAM FIG 4 CONTINUED...
Страница 12: ...12 YORK INTERNATIONAL SINGLE CIRCUIT UNITS FIG 4 CONTINUED LD01713 CONNECTION DIAGRAM ELECTRICAL BOX...
Страница 43: ...YORK INTERNATIONAL 43 FORM 150 40 NM25 DUAL CIRCUIT UNITS FIG 29 CONTINUED ELEMENTARY DIAGRAM LD01716...
Страница 44: ...44 YORK INTERNATIONAL DUAL CIRCUIT UNITS FIG 29 CONTINUED CONNECTION DIAGRAM ELECTRICAL BOX LD01717...
Страница 99: ...YORK INTERNATIONAL 99 FORM 150 40 NM25...