4
YORK INTERNATIONAL
NOTES:
1. Clearances – Minimum YORK required clearances to prevent condenser air recirculation and faulty operation of units are as follows:
Side to wall 8'-0"* Rear to wall 8'-0"* Control Panel End to wall 5'-0"* Top 50'-0" Distance Between Adjacent units 12'-0"
*No more than one wall can be higher than the top of the unit. The area within the clearances shown above and area under the unit must be kept
clear of all obstructions that would impede free air flow to the unit. In installations where winter operation is intended and snow accumulations
are expected, additional unit height must be provided to insure full air flow.
2. Cooler liquid connection sizes (inlet & outlet) 6" victaulic.
3. Dimensions are in inches.
4. Spring Isolators (OPTIONAL) will increase overall height of unit.
DIMENSIONS
YCAQ10, YCAR11
LD01731
Содержание YCAG18
Страница 11: ...YORK INTERNATIONAL 11 FORM 150 40 NM25 SINGLE CIRCUIT UNITS LD01712 ELEMENTARY DIAGRAM FIG 4 CONTINUED...
Страница 12: ...12 YORK INTERNATIONAL SINGLE CIRCUIT UNITS FIG 4 CONTINUED LD01713 CONNECTION DIAGRAM ELECTRICAL BOX...
Страница 43: ...YORK INTERNATIONAL 43 FORM 150 40 NM25 DUAL CIRCUIT UNITS FIG 29 CONTINUED ELEMENTARY DIAGRAM LD01716...
Страница 44: ...44 YORK INTERNATIONAL DUAL CIRCUIT UNITS FIG 29 CONTINUED CONNECTION DIAGRAM ELECTRICAL BOX LD01717...
Страница 99: ...YORK INTERNATIONAL 99 FORM 150 40 NM25...