76
YORK INTERNATIONAL
PROBLEM
CAUSE
SOLUTION
F3 or F7 Fault Code
1. Improper Suction Pressure Cutout
1. Adjust as necessary & restart unit.
Faults on Low Pressure
Adjustment
2. Low Refrig. Charge
2. Repair Leak/Add Refrig.
3. Fouled Filter Drier
3. Change Drier Core
4. Thermal Expansion Valve Adjustment/
4. Adjust Compressor Suction Superheat
Failure
to 11°F (6.1°C) or Replace Power
Element (or Valve)
5. Reduced Flow of Chilled
5. Check GPM (See OPERATING LIMI-
Liquid through Cooler
TATIONS, page 3) Check operation of
pump. Clean Pump Strainer, Purge
Chilled Liquid System of air
6. Check LP Cutout Point on Panel
6. See manual for adjustment procedure
7. Defective Suction Press. Transducer
7. Replace Transducer
8. Fouled Compressor Suction Strainer
8. Remove & Clean Strainer
9. LLSV not opening
9. Check Wiring & LLSV
10. Faulty wiring to Transducer
10. Check wiring
11. Defective Relay Output Board
11. Replace Relay Output Board (Contact
the local YORK service representative.)
12. Defective Combo Board
12. Replace Combo Board (Contact
the local YORK service representative.)
13. Defective Micro Board
13. Replace Micro Board (Contact the
local YORK service representative.)
F4 or F8 Fault Code
1. Condenser fans not operating
1. Check Fans, Fuses, and Contactors.
Cuts out on High Dis-
or rotating backwards.
Air flow must be “UP”.
charge Pressure as
2. Too much Refrigerant
2. Remove Refrigerant
sensed by Micro-Proces-
3. Air in Refrigerant System
3. Evacuate and recharge
sor via high discharge
4. Defective Discharge Press. Transducer
4. Replace Discharge Press. Transducer
pressure transducer.
5. Defective Relay Output Board
5. Replace Relay Output Board (Contact
NOTE: If external H.P.
the local YORK service representative.)
Cut-out Switch trips
6. Defective Combo Board
6. Replace Combo Board (Contact
the Fault Code will be
the local YORK service representative.)
an F1 or F5.
F9 Fault Code
1. Temperature sensed incorrectly
1. Verify actual ambient temperature
Cuts out on high ambient
by thermistor
at probe
temperature. (Max. =
2. Fans Rotating Backwards
2. Air flow must be up. Correct fan
130°F (54.4°C).
rotation.
Will re-start automa-
3. Air flow to unit restricted (or
3. Check installation clearances. (See
tically if temperature
being re-circulated).
page 5.)
drops below
130°F (54.5°C)
F10 Fault Code
1. Temperature of Outside Air is
1. No problem exists.
Cuts out on Low Ambient
below cut-out setting.
Temperature 35°F (1.7°C)
2. Temperature sensed incorrectly
2. Verify actual ambient temperature
min. for Std. Unit. 0°F
by thermistor.
immediately at probe with thermometer.
(–17.8°C) min. for Low
3. Check Low Ambient Temp. Cut-out
3. Adjust if necessary.
Ambient Unit.)
setting on the display (Display Code 7)
NOTE: Operation below
35°F (1.7°C) requires
Low Ambient Accessory.
DUAL CIRCUIT UNITS
Содержание YCAG18
Страница 11: ...YORK INTERNATIONAL 11 FORM 150 40 NM25 SINGLE CIRCUIT UNITS LD01712 ELEMENTARY DIAGRAM FIG 4 CONTINUED...
Страница 12: ...12 YORK INTERNATIONAL SINGLE CIRCUIT UNITS FIG 4 CONTINUED LD01713 CONNECTION DIAGRAM ELECTRICAL BOX...
Страница 43: ...YORK INTERNATIONAL 43 FORM 150 40 NM25 DUAL CIRCUIT UNITS FIG 29 CONTINUED ELEMENTARY DIAGRAM LD01716...
Страница 44: ...44 YORK INTERNATIONAL DUAL CIRCUIT UNITS FIG 29 CONTINUED CONNECTION DIAGRAM ELECTRICAL BOX LD01717...
Страница 99: ...YORK INTERNATIONAL 99 FORM 150 40 NM25...