172
YORK INTERNATIONAL
the code is being keyed in, the digits are not displayed
but are shown as “*” as shown:
When the Enter key is pressed, the following message
will appear:
Key in a “1” for if default setpoints are required, or a
“0” for individually programmed values, then press En-
ter to store the selection into memory.
If individual programming is selected, the display will
now return to the Status display. If a default setpoints
have been selected, the display will momentarily dis-
play the message shown below before returning to the
Status display:
It is often easier to select Default
Setpoints and then reprogram a few
that require changing rather than pro-
gramming each individual value from
scratch.
A list of the default values entered into memory, if this
program option is selected, is shown below:
8.3
PROGRAMMING “DEFAULT” VALUES
Programmable values may be individually programmed
at start-up or any time thereafter. For ease of program-
ming, once the type of refrigerant is programmed in un-
der the Program key, a “defaults password” may be pro-
grammed to automatically program default values into
memory. This will preset all programmable values un-
der the Program key to values that will allow operation
of the chiller under most operating conditions. This al-
lows quick start-up programming for typical chilled wa-
ter applications.
To program the default values into memory, first press
the PROGRAM key followed by the ENTER key, to
program the “refrigerant type.” Press the Program key
again, key in the numbers “6140”, then press Enter. As
P R O G R A M
M O D E
* * * *
D E F A U L T
S E T P O I N T S
?
1
=
Y E S ,
0
=
N O,
1
P R O G R A M
O P T I O N S
S E T
T O
D E F A U L T
V A L U E S
6140
Programmable Value
Default
Setting
Discharge Pressure Cutout
R22
28 bar (399 PSIG)
Low Ambient Cutout
Std. Amb.
-4°C
(25°F)
Low Amb.
-4°C
(25°F)
High Ambient Temperature Cutout
38°C
(130°F)
Discharge Pressure Unload
R22
26 bar (375 PSIG)
High Motor Current Unload
100%
Anti-Recycle Timer
600 sec.
Leaving Chilled Liquid Temp Cutout
2°C
(36°F)
Suction Pressure Cutout
R22
3 bar (44 PSIG)
If manual control is desired, press the
!
!
!
!
!
or
#
#
#
#
#
key. One
of the following messages will be displayed:
System 1, 2, 3 or 4 can be selected as the lead by press-
ing the
!
!
!
!
!
or
#
#
#
#
#
key. The ENTER key must be pressed
to save the selection in memory.
Automatic/Manual Power Failure Restart
The chiller may be selected for “Automatic” or
“Manual” restart after a power failure. In most instances,
“Automatic Restart” is preferred to allow the chiller to
automatically restart when power is reapplied after a
power failure. When “Manual” is selected, the chiller
will not operate after re-application of power until the
ON / OFF Rocker Switch on the keypad is cycled OFF
and then ON.
In most applications, it is undesirable
to use Manual Reset on power failure
since chillers normally are required to
auto-restart after a power failure.
L E A D / L A G
C O N T R O L
M A N U A L
S Y S
2
L E A D
L E A D / L A G
C O N T R O L
M A N U A L
S Y S
1
L E A D
P O W E R
F A I L
R E S T A R T
A U T O M A T I C
MicroPanel Contents
Содержание Millennium YCAS Series
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation ...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank ...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7 ...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7 ...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7 ...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data ...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7 ...