50
YORK INTERNATIONAL
Technical Data
ELECTRICAL DATA
See page 53 for Electrical Data footnotes.
MULTIPLE POINT POWER SUPPLY CONNECTION – 3 & 4 COMPRESSOR UNITS (SEE FIG. 15 OR FIG. 16)
(Two Field Provided Power Supply Circuits to the Chiller. Field Connections to Factory provided Terminal Block (Std)
or Disconnects (Opt) in the Options Panel or Individual System Circuit Breakers (opt
10
) in each of the two Motor Control Centers.)
ELECTRICAL SYSTEM #1 FIELD SUPPLIED WIRING
Field Provided Power Supply
Factory Provided (Lugs)
Compressor #1
Compressor #3
Fan
11, 12
Model
Data
YCAS
Volts
MRA
1
Min NF
Protection
13
Standard
Optional NF
RLA Y-
∆∆∆∆∆
LRA X-LRA RLA Y-
∆∆∆∆∆
LRA X-LRA Qty FLA (ea) LRA (ea)
(MCA) Disc SW
2,9
Min.
3, 5
Max.
4, 6
Terminal block
Disc. Switch
0693
380
362
400
400
450
(1) 2/0-(2)4/0
(2) 3/0-250
140
283
907
124
283
907
7
4.4
17.1
0773
380
436
600
450
500
(2) 1/0-300
(2) 250-500
140
283
907
183
283
907
7
4.4
17.1
0783
380
402
400
450
500
(1) 2/0-(2)4/0
(2) 3/0-250
124
283
907
168
283
907
8
4.4
17.1
0873
380
457
600
500
500
(2) 1/0-300
(2) 250-500
168
283
907
168
283
907
8
4.4
17.1
0953
380
494
600
500
600
(2) 1/0-300
(2) 250-500
183
283
907
183
283
907
8
4.4
17.1
1063
380
413
600
450
500
(2) 1/0-300
(2) 250-500
161
283
907
140
283
907
8
4.4
17.1
1093
380
436
600
450
500
(2) 1/0-300
(2) 250-500
183
283
907
140
283
907
7
4.4
17.1
1163
380
457
600
500
500
(2) 1/0-300
(2) 250-500
168
283
907
168
283
907
8
4.4
17.1
1263
380
494
600
500
600
(2) 1/0-300
(2) 250-500
183
283
907
183
283
907
8
4.4
17.1
Wire Range
7
Over-current
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL SYSTEM
CIRCUIT BREAKERS – 3 & 4 COMPRESSOR UNITS (SEE FIG. 17)
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)
in ‘Option Panel’. Individual System Circuit Breakers in each Motor Control Center.)
See page 53 for Electrical Data footnotes.
FIELD SUPPLIED WIRING
Chiller
Field Provided Power Supply
Factory Provided (Lugs) Wire Range
7
Model
YCAS
Volts MRA
1
Min NF
Over-Current Protection
13
Terminal Block
NF Disc. Switch
(MCA)
Disc SW
2
Min.
3, 5
Max.
4, 6
(Lugs) Wire Range
(Lugs) Wire Range
0693
380
551
600
600
600
(2)2/0-500
(2)250-500
0773
380
625
800
700
700
(2)2/0-500
(3)2/0-400
0783
380
575
600
600
600
(2)2/0-500
(2)250-500
0873
380
685
800
700
700
(3)1/0-300
(3)2/0-400
0953
380
741
800
800
800
(3)1/0-300
(3)2/0-400
1063
380
826
1000
800
800
(3)2/0-500
(4)4/0-500
1093
380
872
1000
1000
1000
(3)2/0-500
(4)4/0-500
1163
380
914
1000
1000
1000
(3)2/0-500
(4)4/0-500
1263
380
989
1000
1000
1000
(3)2/0-500
(4)4/0-500
Содержание Millennium YCAS Series
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation ...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank ...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7 ...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7 ...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7 ...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data ...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7 ...