150
YORK INTERNATIONAL
on the Microprocessor Board. Proper programming of
the switches is important during the commissioning of
the chiller. The Options key can be used to verify the
Dip Switch positions without looking at or handling
the Microprocessor Board.
Each press of the key will scroll to the next option/dip
switch setting.
Three Option Switch Messages (S1-1 to S1-3) will then
be displayed in sequence. At the end of the sequence,
the display will automatically revert to the first Option
Switch message.
The following is a detailed guide to programming the
Dip Switches together with the associated display mes-
sage provided for each selection when the Options key
is pressed:
SWITCH 1: Water / Brine Cooling
Open:
Water Cooling Mode is for water cooling applications
and allows the chilled liquid leaving temperature
setpoint to be programmed from 4 to 21°C (40 to 70
°F). Selecting this mode also auto-programs the Low
Chilled Liquid Cut-Out at 2°C (36°F) and the Suction
Pressure Cut-Out at 3 bar ( 44 PSIG ).
Closed:
Brine Cooling Mode is for brine/glycol applications
with setpoints below 4°C (40°F) and allows the chilled
liquid leaving temperature setpoint to be programmed
from -12 - 21°C (10 to 70°F). In this mode, the Low
Chilled Liquid Cut-Out can be programmed from -13
to 2°C (8 to 36° F) and the Suction Pressure Cut-Out
programmed from 1 to 5 bar (20 to 70 PSIG) for R-22
models and 0.3 to 5 bar (5 to 70 PSIG) for R-407c
models.
This display shows the average motor current in amps
and average compressor motor current as a percentage
of FLA. All values are approximate. Keep in mind that
current in “amps” is an “approximate” value.
On the second press of the of the Motor Current Key,
the current limit values as set by the ISN (Remote BAS
System) and EMS-PWM current limiting input are dis-
played, if they are active. See Sections 1.10, and 2.4
for more details.
3.6
OPERATING HRS / START COUNTER KEY
When the Operating Hours / Starts Counter key is
pressed, the accumulated running hours and starts for
System 1 and 2 compressors are displayed. Where ap-
plicable, pressing the key again displays the values for
Systems 3 and 4 on larger models:
Display Limits :
Maximum run hours 99,999
Maximum starts 99,999
Values roll over to zero, if the maximum limit is ex-
ceeded.
These counters are zeroed at the fac-
tory, but may indicate run time and
number of starts logged during factory
testing prior to shipment.
3.7
OPTIONS KEY &
DIP SWITCH SETTINGS
The Options key provides a display of options which
are programmed by the positions of the S1 Dip Switches
H R S
1 =
1 1 4 3 . 2
=
1 3 8 2
S T R
1 =
2 8 5 . 2
=
3 2 2
H R S
3 =
1 2 5 5 . 4
=
1 0 9 5
S T R
3 =
3 6 5 . 4
=
4 5 5
S 1 - 1
C H I L L E D
L I Q U I D
W A T E R
S 1 - 1
C H I L L E D
L I Q U I D
G L Y C O L
C O M P
1 = 6 3
A M P
8 5 % F L A
C O M P
2 = 3 0
A M P
4 1 % F L A
I S N
C R N T
L I M I T :
N O N E
E M S
C R N T
L I M I T :
N O N E
MicroPanel Contents
Содержание Millennium YCAS Series
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation ...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank ...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7 ...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7 ...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7 ...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data ...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7 ...