154
YORK INTERNATIONAL
System Data:
The following sequence of three displays are provided
first for System 1, then for System 2, and then for Sys-
tems 3 and 4 as applicable.
This message displays the accumulated Run Time since
the last start in Days (D), Hours (H), Minutes (M), and
Seconds (S).
This message indicates the Liquid Line Solenoid Valve
and the economizer TXV solenoid valve position: ON =
Energized/Open, OFF = De-energized/Closed.
This message advises the stage of condenser fan opera-
tion on this system and the status of the compressor
heater. See Section 8.4 for details of fan staging.
Once the System Data sequence has been repeated for
the second system, pressing the
!
!
!
!
!
or
#
#
#
#
#
key again will
loop back to the beginning to the Load/Unload Timer
display. To leave the sequence at any point press a key
from another section of the keypad.
Pressing the “ * ” at any time while in
the OPER DATA mode displays the
EPROM software version being used,
as shown below:
The Local and System Data display messages for the
YCAS 3 and 4 System models follow the same format
as the YCAS 2 System model messages as given in the
preceding paragraphs. The only difference is that after
the System 2 Data is completed, pressing the
!
!
!
!
!
key
displays System 3 and System 4 data before looping
back to the Load/Unload Timer Display.
4.4
OPERATING DATA -
REMOTE PRINTOUT
The follow text shows a typical example printout ob-
tained by pressing the Operating Data key with an op-
tional printer attached. In this case an example is shown
The upper message gives the difference (error) between
actual leaving chilled liquid temperature and the pro-
grammed Target temperature. The lower message gives
the rate of change of the chilled liquid leaving tem-
perature in degrees per minute. A minus sign (-) indi-
cates falling temperature. No sign indicates rising tem-
perature.
This message advises which system is programmed as
the lead.
This message indicates the position of the optional aux-
iliary contacts for the evaporator water pump and the
status of the evaporator heater.
For the evaporator pump contacts, ON = contacts closed,
OFF = contacts open.
The Evaporator Heater status is controlled on ambient
temperature as follows: If measured ambient falls be-
low 4°C (40°F) the Evaporator Heater is switched ON.
If measured ambient then rises above 7°C (45°F) the
heater is switched OFF. The evaporator heater prevents
water standing in the evaporator from freezing.
This message indicates that a remote device such as a
Remote Control Center, an ISN controller, or another
device sending a PWM signal for temperature or cur-
rent reset is overriding control points programmed
through the keypad or default microprocessor setpoints.
The following displays may be encountered:
NONE
–
No remote control active. Remote
monitoring may be active.
ISN
–
YorkTalk via ISN or Remote Control
Center (remote mode).
PWM CURR – EMS PWM Current Limiting Enabled
PWM TEMP – EMS PWM Temp. Reset Enabled
CUR/TEMP – EMS PWM Current Limiting &
Temperature Reset Enabled
T E M P
E R R O R
0 0 . 3
° C
T E M P
R A T E
-
0 . 5
° C / M
L E A D
S Y S T E M
I S
S Y S T E M
N U M B E R
#
E V A P
P U M P
I S
O F F
E V A P
H E A T E R
I S
O N
A C T I V E
R E M O T E
C T R L
N O N E
S Y S
#
F A N
S T A G E
3
C O M P
H E A T E R
I S
O N
S O F T W A R E
V E R S I O N
o
o
o
o
o
C . A 1 4 . 1 0 . 0 1
S Y S
#
R U N
T I M E
1 -
3 - 4 8 - 1 7
D - H - M - S
S Y S
#
L L S V
I S
O N
E C O N
T X V
S O L
I S
O N
MicroPanel Contents
Содержание Millennium YCAS Series
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation ...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank ...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7 ...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7 ...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7 ...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7 ...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data ...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7 ...