FORM 201.10-NM3
77
YORK INTERNATIONAL
Remote Control Mode allows an ISN system or an RCC
(Remote Control Center 60 Hz models only) panel to
receive chiller data from the chiller through the RS-485
port. This mode will also allow programming of load-
ing, unloading, shutdown, Leaving Water Setpoint Re-
set, Current Limit Setpoint, and Lag Start Setpoint from
an ISN or RCC. If communications are lost to the ISN
or RCC, the micro will run the chiller on the locally pro-
grammed values.
SWITCH 4: Expansion Valve Type
Both Positions:
This switch is presently disabled. In the future, it will
allow selection of control from either thermal expan-
sion valves or electronic expansion valves.
SWITCH 5: Units of Measurement
Open:
English Units Mode causes all information relating to
pressures, temperatures, etc., to be displayed in En-
glish (Imperial) units (°F, PSI, etc).
Closed:
S.I. Units Mode causes all information relating to pres-
sures, temperatures, etc., to be displayed in S.I. (Met-
ric) units (°C, BAR, etc.). For conversion purposes,
1BAR = 14.5 PSIG.
SWITCH 6: Compressor Motor Starting
Open:
Across-The-Line Mode MUST be used for chillers with
single contactor Across-the-Line (D.O.L.) starters on
each compressor.
point to be programmed from 38 to 70°F. Selecting this
mode also auto-programs the Low Chilled Liquid Cut-
Out at 36°F and the Suction Pressure Cut-Out at 44
PSIG and are not adjustable.
Closed:
Brine Cooling Mode is for brine / glycol applications
with setpoints below 40°F and allows the chilled liquid
leaving temperature setpoint to be programmed from
10 to 70°F. In this mode, the Low Chilled Liquid Cut-
Out can be programmed from 8 to 36°F and the Suc-
tion Pressure Cut-Out programmed from 20 to 70 PSIG.
SWITCH 2: Ambient Temp. Low Limit
Open:
Standard Ambient Mode fixes the Low Ambient Cut-
Out setting at 25°F (3.9°C) and should normally be
selected if a Low Ambient Kit is NOT installed.
Closed:
Low Ambient Mode allows the Low Ambient Cut-Out to
be programmed from 0 to 50°F. Values above 25°F can
be used to automatically shut down the chiller when
direct cooling methods become operational.
SWITCH 3: Chiller Control
Open:
Local Control Mode allows an ISN system or an RCC
(Remote Control Center 60 Hz models only) panel to
receive chiller data from the chiller through the RS-485
port but not change programmable setpoint values re-
motely.
Closed:
B R I N E
C O O L I N G
L O W
A M B I E N T
C O N T R O L
S T A N D A R D
A M B I E N T
L O C A L
C O N T R O L
M O D E
R E M O T E
C O N T R O L
M O D E
T H E R M A L
E X P A N S I O N
V A L V E S
E N G L I S H
U N I T S
R E A D O U T
S I
U N I T S
R E A D O U T
A C R O S S - T H E - L I N E
M O T O R
S T A R T I N G
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...