![York Millennium YCAS 310 Скачать руководство пользователя страница 113](http://html1.mh-extra.com/html/york/millennium-ycas-310/millennium-ycas-310_installation-operation-and-maintenance_3771726113.webp)
FORM 201.10-NM3
113
YORK INTERNATIONAL
PANEL CHECKS
(Power On – Both System Switches “OFF”)
q
1. Apply 3 phase power and verify its value (See
Fig. 20).
q
2. Apply 115VAC and verify its value on the termi-
nal block in the lower left of the Power Panel.
Make the measurement between terminals 5
and 2 of TB1 (See Fig. 20.). The voltage should
be /- 10%.
q
3. Assure the heaters on each compressor are on.
Allow the compressor heaters to remain on a
minimum of 24 hours before startup. This is im-
portant to assure that no refrigerant is in the com-
pressor oil at start-up!
q
4. Program the dip switches on the microprocessor
board for the desired operating requirements. See
Page 80. OPEN = Left side of switch pushed down.
CLOSED = Right side of switch pushed down.
SW#
OPEN
CLOSED
1
Water
Brine
2
Std Amb
Low Amb
3
Local
Remote
4
N/A
N/A
5
English
SI (Metric)
6
ACL Start
W-D Start
7
M Lead/Lag
A Lead/Lag
8
R- 1 34a
R-22
Verify the selections by pressing the OPTIONS
Key on the control panel. Check them off.
CAUTION: Damage to the chiller could result if
switches are improperly pro-
grammed.
q
5. Program the required twenty-two operating val-
ues into the micro for cut-outs, safeties, etc. and
record them in the chart below. See Page 88.
If Default Values are desired for programming
convenience, press the PROGRAM key, 6140,
and ENTER. This loads default values. Record
these values in the chart below.
PROGRAMMED VALUES
Refrigerant Type = __________________________
Dischg Press Cut-out = ____________ PSIG (kPa)
Low Amb Cut-out = ___________________ °F (°C)
High Amb Cut-out = ____________________ °F (°C)
Disch Press Unld = _________________ PSIG (kPa)
Avg Current Unld = _____________________ %FLA
Anti Recycle Time = _____________________ Secs
LWT Cut-out = ________________________ °F (°C)
Suction Press Cut-out = ____________ PSIG (kPa)
Lag Cmpr Start Point = _________________ %FLA
Lag Compr Diff Off = ___________________ %FLA
Fan Dsch Press Setpt = _____________ PSIG (kPa)
Fan On/Off Press Diff = _____________ PSIG (kPa)
Sys 1 Curr = 100 %FLA = _______________ AMPS
Sys 2 Curr= 100 %FLA = ________________ AMPS
Sys 3 Curr= 100% FLA = _______________ AMPS
Sys 4 Curr= 100% FLA = _______________ AMPS
Liq Inj Temp Limit = ____________________ °F (°C)
Sys 1 Cond Tmp = ______________ °F (°C) = 100%
Sys 2 Cond Tmp = ______________ °F (°C) = 100%
Sys 3 Cond Tmp = _____________ °F (°C) = 100%
Sys 4 Cond Tmp = ______________ °F (°C) = 100%
Com Mode = ISN _________ or RCC __________
Load Share = SV% ________ or %FLA __________
Econ Valve On Point = ________________________
Econ Valve Off Point = ________________________
q
6. Program the Chilled Liquid Temp/Range and
record:
CR = ________ to _________ °F (°C)
Target = ____________ °F (°C)
Keep in mind that the Target temperature dis-
played by the micro should equal the desired
leaving water temperature.
q
7. Assure that the CLK jumper J18 on the Micro-
processor Board is in the ON position (Top 2
pins).
q
8. Set the Time and Date.
q
9. Program the Daily Schedule start and stop times.
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...