YORK INTERNATIONAL
14
STANDARD COMPRESSOR POWER SUPPLIES
(Each Compressor System Power Supply Individually Protected with Field Supplied Branch Circuit Protection)
NOTES for Electrical Data
:
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other
loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system
#1 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440-12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per
N.E.C. 440-22.
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2.
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), (3) or (4)
preceeding the wire range indicates the number of termination points or lugs which are available per phase. The (1-2), (1-3) or (1-4)
preceeding the wire range indicates that a single multi-termination lug is available per phase that can accept from two (1-2) to four (1-4) wires
of the wire range specified (1) #1-600MCM OR (2) #1-250MCM indicates that a single lug is supplied and it will accept a single wire up to
600MCM or 2 wires up to 250MCM. Actual wired size and number of wires per phase must be determined based on ampacity and job
requirements using N.E.C. wire sizing information. The above recommendations are based onthe National Electrical Code and using copper
connectors only. FIeld wiring must also comply with local codes.
8. A ground lug is provided from each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6-350MCM.
9. The supplied disconnect is a Disconnecting Means as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
LEGEND
ACR-LINE
ACROSS THE LINE
CB
CIRCUIT BREAKER
DE FU
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT MOUNT CB
FACTORY MOUNTED CIRCUIT BREAKER
FACT MOUNT FUSE FACTORY MOUNTED FUSES
FLA
FULL LOAD AMPS
HZ
HERTZ
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN
MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RUNNING LOAD AMPS
VOLTAGE CODE
S.P. WIRE
SINGLE POINT WIRING
17 = 200-3-60
UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON FUSED DISCONNECT SWITCH)
28 = 230-3-60
WYE-DELTA
WYE-DELTA START
40 = 380-3-60
XLRA
ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS
46 = 460-3-60
YLRA
WYE-DELTA INRUSH LOCKED ROTOR AMPS
58 = 575-3-60
ELECTRICAL DATA
SYSTEM #1 & #3 (EACH) FIELD SUPPLIED WIRING
MODEL
VOLTS
MCA
1
MIN NF
D.E. FU
C.B.
WIRE RANGE
7
(LUGS)
COMPRESSOR
FANS
DISC SW
2
MIN.
3
MAX.
4
MIN.
5
MAX.
6
WYE-DELTA
ACR-LINE
RLA Y LRA X LRA
FLA (EA)
380
334
400
400
500
400
500
(2) #6 - 250
NA
250
401
N/A
5.2
YCAS310
460
268
400
350
450
350
400
(2) #6 - 250
1/0 - 500
198
331
1051
5.0
575
218
400
300
350
300
350
(2) #6 - 250
#6 - 250
158
145
463
4.9
380
415
400
500
700
500
700
(2) 1/0 - 500
NA
315
483
NA
5.2
YCAS340
460
333
400
400
500
400
500
(2) #6 - 250
1/0 - 500
250
398
1261
5.0
575
269
400
350
450
350
400
(2) #6 - 250
1/0 - 500
199
311
987
4.9
380
415
400
500
700
500
700
(2) 1/0 - 500
NA
315
483
NA
5.2
YCAS360
460
333
400
400
500
400
500
(2) #6 - 250
1/0 - 500
250
398
1261
5.0
575
269
400
350
450
350
400
(2) #6 - 250
1/0 - 500
199
311
987
4.9
380
439
600
600
700
600
700
(2) 1/0 - 500
NA
334
483
NA
5.2
YCAS380
460
352
400
450
600
450
500
(2) #6 - 250
1/0 - 500
265
398
1261
5.0
575
284
400
350
450
350
450
(2) #6 - 250
1/0 - 500
311
311
987
4.9
CONTROL POWER SUPPLY
UNIT
CONTROL
MIN
MAX DUAL
NON-FUSED
VOLTAGE
POWER
CIRCUIT
ELEMENT
DISC. SW.
SUPPLY
AMPACITY
FUSE SIZE
SIZE
STD.
MODELS W/O
115-1-60
20A
20A
30A
TRANSFORMERS
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...