YORK INTERNATIONAL
66
This message indicates that the Chiller On (Auto) / Off
Switch on the Control Panel is in the Off position which
will not allow the chiller to run.
Schedule Shutdown:
This message indicates that the chiller has been shut
down by the daily schedule programmed into the Clock
Set Schedule / Holiday system.
Compressors Running:
This message indicates that the respective compres-
sor is running due to demand.
System Switches OFF:
This message indicates that the system switch on the
Microprocessor Board for the respective system is in
the Off position. A system can only run if the system
switch is in the On position. The switch for System 1
and System 2 should normally be in the On position for
all models. Switches for System 3 and 4 should only
be in the On position for three or four compressor chill-
ers respectively. See Section 1.8, page 8, for the loca-
tion of the system switches.
2. STATUS KEY & FAULT MESSAGES
2.1 GENERAL
Pressing the Status key displays the current chiller or
individual system operational status. The messages
displayed include running status, cooling demand, fault
status, external cycling device status, load limiting, and
anti-recycle timer status. The display will show one
message relating to the highest priority information to
be displayed as determined by the Microprocessor.
For individual system status or fault messages the dis-
play shows information for up to two refrigerant sys-
tems. For models with three or four systems, pressing
the Status key again will scroll through messages for
all systems.
The main categories of messages available using the
Status key are:
General Status Messages
Anticipation Control Status Messages
Chiller Fault Status Messages
System Fault Status Messages
These messages are described in detail below, with
examples of each display. In each example # is used
as applicable to represent the system number where
messages apply to individual systems.
2.2 GENERAL STATUS MESSAGES
Unit Switch Off:
U N I T
S W I T C H
I S
I N
T H E
O F F
P O S I T I O N
D A I L Y
S C H E D U L E
S H U T D O W N
S Y S
#
C O M P
R U N N I N G
S Y S
#
C O M P
R U N N I N G
S Y S
#
S Y S
S W I T C H
O F F
S Y S
#
S Y S
S W I T C H
O F F
28164(b)A
STATUS
KEY
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...