![York Millennium YCAS 310 Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/york/millennium-ycas-310/millennium-ycas-310_installation-operation-and-maintenance_3771726102.webp)
YORK INTERNATIONAL
102
100.0 - 130.0°F are accepted. This programmable value
is password protected.
To program the High Ambient Cutout, key in the re-
quired setting and press the Enter key to store the value
into memory and scroll to the next display.
High Discharge Pressure Unload Point
The Discharge Pressure Unload point is used to avoid
a high pressure cutout shutdown by unloading a com-
pressor if its discharge pressure approaches the cut-
out value. The chiller can then continue to run auto-
matically at reduced capacity until the cause of the ex-
cessive pressure is attended to (e.g. dirty condenser
coils) or ceases naturally (e.g. high ambient tempera-
ture).
For the first 60 seconds of operation discharge pres-
sure limiting is disabled. After this time, if discharge pres-
sure exceeds the programmed limit, a 1 second unload
pulse will be sent to the slide valve of the affected com-
pressor every 5 seconds until the discharge pressure
drops below the programmed limit. The message will be
removed and reloading take place when discharge pres-
sure has dropped 60 PSIG below the threshold.
Typically, the unload point should be set 20 - 25 PSI
below the discharge pressure cutout setting. The micro
will accept a range of programmable values between
200 - 390 PSIG for R22 models, 128 - 270 PSIG for
R134a models. This programmable value is password
protected.
To program the Discharge Pressure Unload, key in the
required setting and press the Enter key to store the
value into memory and scroll to the next display.
High Average Current Unload Point
The Average Current Unload point is used to avoid a
high motor current safety shutdown by unloading a com-
pressor if its current draw approaches the maximum
limit cutout value. The chiller can then continue to run
automatically at reduced capacity until the cause of the
excessive current is attended to.
The micro will accept between 30 - 115% for the un-
load point. The motor current safety will shut the com-
pressor down whenever current exceeds 115%.
If the programmable limit is set between 100% and 115%
of full load current, this safety will protect against exces-
sive current which would cause compressor shutdown
due to extremely high ambient, high chilled liquid tem-
perature, and condenser malfunction caused by dirt or
fan problems.
If the programmable limit is set below 100% of full load
current, this feature can be used for demand limiting.
This is important when demand limiting is critical due
to power requirements or limitations in the building (See
also Section 1.7).
For the first 60 seconds of operation, the unloading
safety is disabled. After this time, if motor current ex-
ceeds the programmed limit the SYS X CRNT LIMIT-
ING message will appear and a 1 second unload pulse
will be sent to the slide valve of the affected compres-
sor every 5 seconds until the motor current drops be-
low the programmed limit. The message will be re-
moved and additional loading will take place when
motor current drops below the programmed threshold.
Typically, this setpoint should be set at 100 - 105%.
It is not recommended to program a value greater
than 105%. For maximum motor protection, pro-
gramming for 100% is advisable.
When programming
values below 100% use of a leading 0 is required,
e.g. 085%.
To program the Average Motor Current Unload, key in
the required setting and press the Enter key to store
the value into memory and scroll to the next display.
Anti-Recycle Timer
The Anti-Recycle Timer controls the minimum time be-
tween starts for each compressor. This is the time avail-
able for the heat build-up caused by inrush current at
start to be dissipated before the next start. Insufficient
cooling time between starts can cause heat build-up
and motor damage. A fast compressor start response
is needed in some applications and not in others. Al-
though the minimum setting allowed on this timer will
avoid excessive heat build-up, adjusting the timer for
the longest period acceptable in each application will
reduce cycling and maximize motor life.
600 seconds
is recommended.
The micro will accept a range of programmable values
between 300 - 600 seconds.
To program the Anti-Recycle Timer, key in the required
setting and press the Enter key to store the value into
memory and scroll to the next display.
D I S C H A R G E
P R E S S U R E
U N L O A D
=
3 6 0 . 0
P S I G
A V E R A G E
C U R R E N T
U N L O A D
=
1 0 5
% F L A
A N T I
R E C Y C L E
T I M E R
=
6 0 0
S E C S
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...