FORM 201.10-NM3
111
YORK INTERNATIONAL
YCAS 310-380 FAN CONTROL STRATEGY
The chiller is equipped with 12 condenser fans; 4 per
system. Fan control from discharge pressure is stan-
dard. Fan start/stop pressures are programmable in
the PROGRAM Mode (Section 8) under FAN CON-
TROL DISCHARGE PRESSURE SETPOINT and FAN
ON/OFF PRESS DIFF displays. Ambient temperature
has no effect on fan cycling.
When discharge pressure reaches the programmed
setpoint, the first pair of fans on a respective system
starts. After the first pair of fans are brought on in the
reverse direction, discharge pressure must rise an ad-
ditional 20 PSIG above the setpoint before a second
pair of fans will be brought on in the forward direction.
When this pair of fans starts, the reversing fans will
turn off. If discharge pressure rises 40 PSIG above the
setpoint, a second pair of fans will start in the forward
direction. This is the same pair of fans that originally
ran in the reverse direction. The first pair of forward
fans will also continue to run.
The point at which each pair of fans cycles off is also
programmable. This is accomplished in the PROGRAM
Mode when the FAN ON/OFF PRESS DIFF display
appears. The progammable differential establishes
the pressure at which each pair of fans turn off. The
differential is the amount the discharge pressure must
drop below the pressure at which the fan turned on.
Locations of the fans and a table showing the opera-
tion is shown in Fig. XX.
PRESSURE
FAN
FAN RELAY
ON
OFF
1 & 2 REV
9M & 10M
SETPOINT
SETPOINT - DIFF.
(SYS 1)
OR
5 & 6 REV
15M & 16M
SETPOINT
SETPOINT - DIFF.
(SYS 2)
OR
9 & 10 REV
9M & 10M
SETPOINT
SETPOINT - DIFF.
(SYS 3)
3 & 4 FOR
6M & 8M
SETPOINT (SE 20 PSIG)
(SYS 1)
+ 20 PSIG
- DIFF.
OR
7 & 8 FOR
12M & 14M
SETPOINT (SE 20 PSIG)
(SYS 2)
+ 20 PSIG
- DIFF.
OR
11 & 12 FOR
6M & 8M
SETPOINT (SE 20 PSIG)
(SYS 3)
+ 20 PSIG
- DIFF.
1 & 2 FOR
5M & 7M
SETPOINT (SE 40 PSIG)
(SYS 1)
+ 40 PSIG
- DIFF.
OR
5 & 6 FOR
11M & 13M
SETPOINT (SE 40 PSIG)
(SYS 2)
+ 40 PSIG
- DIFF.
OR
9 & 10 FOR
5M & 7M
SETPOINT (SE 40 PSIG)
(SYS 3)
+ 40 PSIG
- DIFF.
FIG. XX
YCAS 310-380 FAN LOCATION/OPERATION
LD03124
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...