FORM 201.10-NM3
73
YORK INTERNATIONAL
A/L Start:
Dial Setting = (1.1 x RLA) / 350
WYE-Delta Start:
Dial Setting = (0.64 x RLA) / 350
The Mechanical HP (Hight Pressure) Cut-out will also
cause the low current safety to activate. If discharge
pressure exceeds 405 PSIG (HP cut-out), the cut-out
will open. When the cut-out opens, 115VAC power will
be removed from the Motor Protector Module. When
power is removed from the module, its MP contacts
will open, breaking the 115VAC fed to the 1CR (Sys 1)
or 2CR (Sys 2) control relay. When a control relay is
de-energized, power is removed from the compressor
contactors which shuts the compressor off. When the
motor contactor de-energizes, motor current falls to
zero. The low motor current is sensed by the micropro-
cessor and the system is shut down.
Auto-restart will be permitted after shutdown, when dis-
charge pressure drops below 330 PSIG and the HP
contacts close. A fault lock-out will result if safety thresh-
olds are exceeded three times in a 90 minute period.
2.6 PRINTOUT ON FAULT SHUTDOWN
If an optional printer is installed, the contents of History
Buffer #1 will be sent to the printer any time a fault shut-
down occurs. This will allow record keeping of individual
faults, even if they do not cause a lockout of the system.
This information may be useful in identifying developing
problems and troubleshooting. See also Section 4.7.
The No Run Permissive fault messages will not be
stored in the History Buffer and will not cause an auto
printout.
NOTE: Due to extreme operating conditions or sys-
tems where control deficiencies are present,
occasional faults may occur with the automatic
printout. This is not a cause for concern.
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...