FORM 201.10-NM3
101
YORK INTERNATIONAL
ure to properly program these values may
cause damage to the chiller or operating prob-
lems.
8.2 PROGRAM KEY
USER PROGRAMMABLE VALUES
Refrigerant Type
The Refrigerant Type value is used to program the
chiller for the type of refrigerant and is password pro-
tected. This value MUST be programmed correctly.
Failure to do so may cause serious damage to the
chiller. The type of refrigerant used on individual mod-
els is noted in the Engineering Data stamped on the
chiller nameplate.
To program for R22, key in 022. To program for R134a
key in 134. Press the Enter key to store the pro-
grammed value into memory.
NOTE: The type of refrigerant programmed must match
the refrigerant selected on the SW1 Dip Switch
on the Microprocessor Board. These selections
can be viewed by pressing the Options key (see
Section 3.7). If these two selections do not
match, the following message will appear:
The chiller will not operate until this situation is
corrected.
High Discharge Pressure Cutout
The Discharge Pressure Cutout is a microprocessor
backup for the mechanical high pressure cutout located
in each refrigerant circuit. This safety is bypassed for the
first 5 seconds of operation after which if the cutout point
is exceeded for 3 seconds, the system will shut down.
Normally air-cooled chillers such as YCAS/YDAS chill-
ers should have the cutout set at 395 PSIG for R22
models and 275 PSIG for R134a models. The micro
will, however, accept values between 200 - 399 PSIG
for R22 models and between 128 - 275 PSIG for R134a
models. For this cutout to be functional, the Discharge
Pressure Readout Option must be installed (fitted as
standard on 50 Hz models). This programmable value
is password protected.
To program the Discharge Pressure Cutout, key in the
desired value and press the Enter key to store the value
into memory and scroll to the next display.
Low Ambient Temperature Cutout
The Low Ambient Cutout is used to select the ambient
temperature below which the chiller may not operate.
If the ambient temperature falls 1°F below this point,
the chiller will shut down. Restart will occur automati-
cally, when temperature rises more than 1°F above the
cutout and cooling demand is present (see also Sec-
tion 2.4). This programmable value is password pro-
tected.
If the SW1 Dip Switch on the Microprocessor Board is
set for Standard Ambient Control (see Section 3.7)
the low ambient cutout is set at 25°F and is NOT pro-
grammable. If the Dip Switch is set for Low Ambient
Control, programming of the cutout between 00.0° -
50.0°F is allowed. This allows higher values than 25°F
to be programmed to shut down the chiller when direct
cooling methods become operational. Values below
25°F can be used for applications requiring chiller op-
eration at lower temperatures. If operation is occasion-
ally needed below 1°F, the cutout should be set at
00.0°F. This will allow operation at any temperature as
the micro will only recognize temperatures above 1°F.
Temperatures below 1°F will not be displayed.
To program the Low Ambient Cutout, key in the required
setting and press the Enter key to store the value into
memory and scroll to the next display.
NOTE: Operation below 1°F may occasionally cause
nuisance low pressure safety shutdowns. This
will not cause a problem provided ambient tem-
perature is not expected to be below 1°F for
more than a short time.
High Ambient Temperature Cutout
The High Ambient Cutout is used to select the ambient
temperature above which the chiller may not operate. If
the ambient temperature rises 1°F above this point, the
chiller will shut down. Restart will occur automatically,
when temperature falls more than 1°F below the cutout
and cooling demand is present.
This cutout is normally set at 130°F to allow operation to
the absolute maximum temperature capability of the elec-
tromechanical components, however, values between
R E F R I G E R A N T
T Y P E
2 2
O R
1 3 4
2 2
R E P R O G R A M
T Y P E
O F
R E F R I G E R A N T
T O
R U N
D I S C H A R G E
P R E S S U R E
C U T O U T
=
3 9 5 . 0
P S I G
L O W
A M B I E N T
T E M P
C U T O U T
=
2 5 . 0 ° F
H I G H
A M B I E N T
T E M P
C U T O U T
=
1 3 0 . 0 ° F
Содержание Millennium YCAS 310
Страница 11: ...FORM 201 10 NM3 11 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS English Units LD01594 LD01593...
Страница 13: ...FORM 201 10 NM3 13 YORK INTERNATIONAL YCAS 310 380 DIMENSIONS SI Units LD01598 LD01597...
Страница 21: ...FORM 201 10 NM3 21 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 36: ...YORK INTERNATIONAL 36 YCAS 310 380 SYSTEMS 1 AND 2 CONNECTION DIAGRAM WYE DELTA START LD02032...
Страница 37: ...FORM 201 10 NM3 37 YORK INTERNATIONAL LD02033...
Страница 38: ...YORK INTERNATIONAL 38 YCAS 310 380 SYSTEMS 1 AND 2 WIRING DIAGRAM WYE DELTA START LD03094 LD03095 LD03096...
Страница 42: ...YORK INTERNATIONAL 42 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD02038...
Страница 43: ...FORM 201 10 NM3 43 YORK INTERNATIONAL LD02039...
Страница 44: ...YORK INTERNATIONAL 44 YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM WYE DELTA START LD03098 LD03097 LD03099...
Страница 48: ...YORK INTERNATIONAL 48 LD02021...
Страница 53: ...FORM 201 10 NM3 53 YORK INTERNATIONAL YCAS 310 380 SYSTEM 3 CONNECTION DIAGRAM ACROSS THE LINE START LD02026...
Страница 54: ...YORK INTERNATIONAL 54 LD02027...
Страница 123: ...FORM 201 10 NM3 123 YORK INTERNATIONAL...