58
YORK INTERNATIONAL
FORM 201.18-NM9 (602)
Technical Data
ELECTRICAL DATA (60 HZ)
MULTIPLE POINT POWER SUPPLY CONNECTION 3 & 4 COMPRESSOR UNITS (SEE FIG. 18 or 19)
(Two Field-Provided Power Supply Circuits To The Chiller. Field Connections to Factory-Provided Terminal Block (Std) or Disconnects (Opt)
in the Options Panel. Factory-wired Terminal Blocks or Individual System Circuit Breakers (Opt
10
) in each of the two Motor Control Centers.)
SYSTEM #1 FIELD-SUPPLIED WIRING
FACTORY-PROVIDED (LUGS)
MODEL
VOLTS
MIN NF
WIRE RANGE
7
COMPRESSOR #3
FANS
11, 12
YCAS
MCA
1
DISC SW
2, 9
STD. TERMINAL
OPT. NF.
RLA Y-D-LRA XL-LRA RLA Y-D-LRA XL-LRA QTY
FLA LRA
MIN.
3, 5
MAX.
4, 6
BLOCK
DISC SW.
(EA.) (EA.)
380
326400
350
400
2/0 - 500
(2) 3/0 - 250
121
285
900
121
285
900
8
5.1
21.0
0218EB
460
278
400
300
350
2/0 - 500
(2) 3/0 - 250
100
228
719
100
228
719
8
5.2
29.0
575
220
250
250
250
2/0 - 500
#6 - 350
80
182
574
80
182
574
8
3.9
25.9
380
441
600
500
600
(2) 1/0 - 300
(2) 250-500
121
285
900
213
343
1093
8
5.1
21.0
0248EB
460
373
400
450
500
2/0 - 500
(2) 3/0 - 250
100
228
719
176
280
893
8
5.2
29.0
575
296400
350
400
2/0 - 500
(2) 3/0 - 250
80
182
574
141
224
714
8
3.9
25.9
380
4266
00
500
500
(2) 1/0 - 300
(2) 250-500
165
343
1093
165
343
1093
8
5.1
21.0
0268EB
460
361
400
400
450
2/0 - 500
(2) 3/0 - 250
137
280
893
137
280
893
8
5.2
29.0
575
285
400
350
350
2/0 - 500
(2) 3/0 - 250
109
224
714
109
224
714
8
3.9
25.9
380
485
600
600
600
(2) 1/0 - 300
(2) 250-500
212
343
1093
166343
1093
8
5.1
21.0
0288EB
460
410
600
450
500
2/0 - 500
(2) 250-500
176280
893
137
280
893
8
5.2
29.0
575
325
400
400
400
2/0 - 500
(2) 3/0 - 250
141
224
714
109
224
714
8
3.9
25.9
380
473
600
600
600
(2) 1/0 - 300
(2) 250-500
195
343
1093
166343
1093
9
5.1
21.0
0308EB
460
402
600
450
500
2/0 - 500
(2) 3/0 - 250
161
280
893
137
280
893
9
5.2
29.0
575
318
400
350
400
2/0 - 500
(2) 3/0 - 250
129
224
714
109
224
714
9
3.9
25.9
380
492
600
600
600
(2) 1/0 - 300
(2) 250-500
195
343
1093
184
343
1093 11
5.1
21.0
0328EB
460
417
600
450
500
(2) 1/0 - 300
(2) 250-500
161
280
893
152
280
893 11
5.2
29.0
575
330
400
400
450
2/0 - 500
(2) 3/0 - 250
129
224
714
122
224
714 11
3.9
25.9
380
427
600
500
500
(2) 1/0 - 300
(2) 250-500
166
343
1093
166
343
1093
8
5.1
21.0
0358EB
460
363
400
400
450
2/0 - 500
(2) 3/0 - 250
138
280
893
138
280
893
8
5.2
29.0
575
285
400
350
350
2/0 - 500
(2) 3/0 - 250
109
224
714
109
224
714
8
3.9
25.9
380
473
600
600
600
(2) 1/0 - 300
(2) 250-500
194
343
1093
166343
1093
9
5.1
21.0
0398EB
460
403
600
450
500
2/0 - 500
(2) 3/0 - 250
162
280
893
138
280
893
9
5.2
29.0
575
318
400
350
400
2/0 - 500
(2) 3/0 - 250
129
224
714
109
224
714
9
3.9
25.9
380
526
600
600
700
(2) 2/0 - 500
(2) 250-500
196343
1093
213
343
1093
9
5.1
21.0
0418EB
460
444
600
500
600
(2) 1/0 - 300
(2) 250-500
162
280
893
176
280
893
9
5.2
29.0
575
353
400
400
450
2/0 - 500
(2) 3/0 - 250
129
224
714
141
224
714
9
3.9
25.9
See page 62 for Electrical Data footnotes.
OVER-CURRENT
PROTECTION
FIELD-PROVIDED POWER SUPPLY
COMPRESSOR #1
TABLE 17
MULTIPLE POINT POWER SUPPLY CONNECTION 3 & 4 COMPRESSOR UNITS
Содержание eco YCAS Series
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 77: ...77 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 81: ...81 YORK INTERNATIONAL FORM 201 18 NM9 602 LD04179 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM9 602 7 LD04181 Box Information continued from page 82...
Страница 97: ...97 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 103: ...FORM 201 18 NM9 602 YORK INTERNATIONAL YORK INTERNATIONAL 103 103A LD04267 FORM 201 18 NM9 602...
Страница 163: ...163 YORK INTERNATIONAL FORM 201 18 NM9 602 COMPRESSOR COMPONENTS CONT D FIG 69 COMPRESSOR COMPONENTS CONT D LD03670 7...