4 / 4 / 4 Configuration
5 / 5 / 6 Configuration
3 / 3 / 4 Configuration
5 / 5 / 4 Configuration
8.4
3 COMPRESSOR
CONDENSER FAN CONTROL
The chiller is equipped with 10, 12, 14 or 16 condenser
fans, with 3, 4, 5 or 6 fans per system as given below.
Fan control is via Outside Ambient Temperature (OAT)
and Discharge Pressure (DP). There are six stages of
fan control utilizing 3 outputs per system. The fan stages
will operate according to Tables 50 - 53 depending on
the number of fans/system. There will be a minimum 5
second delay between all fan stages.
Condenser fan ON conditions are governed solely by
the Discharge Pressure (DP). When the DP rises above
220 PSIG, fan stage 1 is activated. From here, subse-
quent fan stages are activated as the DP rises in incre-
ments of 15 PSIG, except stage 6, which is activated
when the DP rises over 290 PSIG. The system will re-
main at the highest fan stage reached unless the OFF
conditions given in the next paragraph are satisfied.
Condenser fan OFF conditions are governed by both
the DP and OAT. Fan staging will be decreased from
the highest stage reached if both the DP and OAT re-
quirements are met. For example, if a system is at a fan
stage of 4, and the DP falls under 195 PSIG and the
OAT drops below 75°F, the fan stage will be reduced to
3. The ON/OFF conditions are provided in the next two
tables.
The tables below also indicate fan contactors, wire num-
bers, and Relay Output Board or I/O Expansion Board
Output numbers relating to fans energized. SYS 1 fan
contactors are controlled by Relay Output Board # 1.
SYS 2 by Relay Output Board # 2. SYS 3 is controlled
by I/O Expansion Board #2.
FIG. 75
CONDENSER FAN CONTROL LAYOUT FOR DXST COMPRESSOR UNITS
LD05022
Micro Panel Contents
Содержание eco YCAS Series
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 77: ...77 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 81: ...81 YORK INTERNATIONAL FORM 201 18 NM9 602 LD04179 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM9 602 7 LD04181 Box Information continued from page 82...
Страница 97: ...97 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 103: ...FORM 201 18 NM9 602 YORK INTERNATIONAL YORK INTERNATIONAL 103 103A LD04267 FORM 201 18 NM9 602...
Страница 163: ...163 YORK INTERNATIONAL FORM 201 18 NM9 602 COMPRESSOR COMPONENTS CONT D FIG 69 COMPRESSOR COMPONENTS CONT D LD03670 7...