194
YORK INTERNATIONAL
FORM 201.18-NM9 (602)
SWITCH 2: Ambient Temp. Low Limit
Open:
Standard Ambient Mode auto-programs the Low
Ambient Cutout setting at 25°F (-4°C) and is not
adjustable.
Closed:
Low Ambient Mode allows the Low Ambient Cutout
to be programmed from 0 to 50°F (-18 to 10°C). Val-
ues above 25°F (-4°C) can be used to automatically
shut down the chiller when direct cooling methods be-
come operational.
SWITCH 3: Refrigerant
Open:
The R-407C Mode MUST be selected for models us-
ing refrigerant R-407C. Incorrect selection of this
switch may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.
S 1 - 2
A M B I E N T
C O N T R O L
S T A N D A R D
S 1 - 2
A M B I E N T
C O N T R O L
L O W
A M B I E N T
S 1 - 3
R E F R I G E R A N T
R - 4 0 7 C
S 1 - 3
R E F R I G E R A N T
R - 2 2
Dip Switch Physical Location and Setting
FIG. 74
ENLARGED PHOTOGRAPH OF DIP
SWITCHES ON MICROPROCESSOR
BOARD
LD03511A
LD03511B
OPEN Position:
Left side of switch
pushed in
CLOSED Position:
Right side of switch
pushed in
Micro Panel Contents
Содержание eco YCAS Series
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 77: ...77 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 81: ...81 YORK INTERNATIONAL FORM 201 18 NM9 602 LD04179 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM9 602 7 LD04181 Box Information continued from page 82...
Страница 97: ...97 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 103: ...FORM 201 18 NM9 602 YORK INTERNATIONAL YORK INTERNATIONAL 103 103A LD04267 FORM 201 18 NM9 602...
Страница 163: ...163 YORK INTERNATIONAL FORM 201 18 NM9 602 COMPRESSOR COMPONENTS CONT D FIG 69 COMPRESSOR COMPONENTS CONT D LD03670 7...