168
YORK INTERNATIONAL
FORM 201.18-NM9 (602)
Dip switches 4 through 8 are spares
and have no function.
q
5. Program the required operating values into the
micro for cutouts, safeties, etc. and record them
in the chart below. See Page 211 for details.
If Default Values are desired for programming
convenience, press the PROGRAM key, 6140,
and ENTER. This loads default values. Record
these values in the chart below.
PROGRAMMED VALUES
Refrigerant Type = __________________________
Dischg Press Cutout = ______________ PSIG (kPa)
Dischg Press Unld = ________________ PSIG (kPa)
Suction Press Cutout = ______________ PSIG (kPa)
High Amb Cutout = ____________________ °F (°C)
Low Amb Cutout = ____________________ °F (°C)
Leaving Chilled Liquid Temp Cutout = ______ °F (°C)
High Motor Current Unload = _____________ % FLA
Anti-Recycle Time = ____________________ Secs
q
6. Program the Chilled Liquid Setpoint/Range and
record:
Setpoint = __________________ °F (°C)
Range = ________ to ________ °F (°C)
Keep in mind that the Target temperature dis-
played by the micro should equal the desired
leaving water temperature.
q
7. Assure that the CLK jumper J18 on the Micro-
processor Board is in the ON position (Top 2
pins).
q
8. Set the Time and Date.
q
9. Program the Daily Schedule start and stop times.
Panel Checks
(Power ON Both System Switches OFF)
q
1. Apply 3-phase power and verify its value (See
Fig. 8, page 37).
q
2. Apply 115VAC and verify its value on the ter-
minal block in the lower left of the Power Panel.
Make the measurement between terminals 5 and
2 (See Fig. 13, page 42). The voltage should be
/- 10%.
q
3. Assure the heaters on each compressor are on.
Allow the compressor heaters to remain on a
minimum of 24 hours before startup. This is im-
portant to assure that no refrigerant is in the com-
pressor oil at start-up!
q
4. Program the dip switches on the microproces-
sor board for the desired operating requirements.
See page 194. OPEN = Left side of switch
pushed down. CLOSED = Right side of switch
pushed down.
Verify the selections by pressing the OPTIONS
Key on the control panel. Check them off.
Damage to the chiller could result if
switches are improperly programmed.
q
14. Assure that evaporator TXV bulbs are strapped
onto the suction lines at 4 or 8 oclock posi-
tions.
q
15. Assure that 5 ton TXV bulbs are inserted fully
into the wells in the compressors and that the
bulbs are coated with heat conductive com-
pound.
q
16. Assure that the 15 ton economizer TXV bulbs
are strapped onto the compressor economizer
supply lines at 4 or 8 oclock positions.
SWITCH
SWITCH OPEN
SWITCH CLOSED
SETTING
SETTING
1
Water Cooling
Brine Cooling
2
Standard Ambient
Low Ambient
Control
Control
3
Refrigerant R-407C
Refrigerant R-22
Technical Data
Содержание eco YCAS Series
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 77: ...77 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 81: ...81 YORK INTERNATIONAL FORM 201 18 NM9 602 LD04179 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM9 602 7 LD04181 Box Information continued from page 82...
Страница 97: ...97 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Страница 103: ...FORM 201 18 NM9 602 YORK INTERNATIONAL YORK INTERNATIONAL 103 103A LD04267 FORM 201 18 NM9 602...
Страница 163: ...163 YORK INTERNATIONAL FORM 201 18 NM9 602 COMPRESSOR COMPONENTS CONT D FIG 69 COMPRESSOR COMPONENTS CONT D LD03670 7...