ZQ04-06 Side Duct Application (Belt Drive)
Table 25: ZQ04 (3.0 Ton) Side Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
n/a
n/a
877
0.25
965
0.34
1050
0.44
1133
0.54
1213
0.64
1292
0.74
1371
0.83
1450
0.92
1531
1.01
1000
795
0.21
887
0.29
976
0.38
1061
0.48
1143
0.58
1224
0.68
1303
0.78
1382
0.87
1461
0.96
1541
1.05
1100
806
0.25
899
0.34
988
0.43
1073
0.53
1155
0.63
1236
0.73
1315
0.83
1394
0.92
1473
1.01
1553
1.09
1200
820
0.31
913
0.39
1002
0.48
1087
0.58
1169
0.68
1249
0.78
1329
0.88
1407
0.97
1487
1.06
1567
1.15
1300
836
0.37
929
0.45
1018
0.54
1103
0.64
1185
0.74
1265
0.84
1345
0.94
1423
1.03
1503
1.12
1583
1.21
1400
855
0.43
948
0.52
1036
0.61
1121
0.70
1204
0.80
1284
0.90
1363
1.00
1442
1.10
1521
1.19
--
--
1500
876
0.50
969
0.58
1058
0.68
1143
0.77
1225
0.87
1305
0.97
1385
1.07
1464
1.17
1543
1.26
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
--
Exceeds recommended Blower speed
1
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
Table 26: ZQ05 (4.0 Ton) Side Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
893
0.37
976
0.46
1054
0.56
1128
0.66
1199
0.75
1268
0.85
1336
0.94
1404
1.03
1474
1.12
1545
1.20
1300
910
0.43
993
0.52
1071
0.62
1144
0.72
1216
0.81
1285
0.91
1353
1.00
1421
1.09
1491
1.18
1562
1.26
1400
931
0.49
1014
0.59
1092
0.69
1166
0.78
1237
0.88
1306
0.97
1374
1.06
1442
1.15
1512
1.24
1583
1.33
1500
956
0.56
1039
0.66
1117
0.76
1191
0.85
1262
0.95
1331
1.04
1399
1.14
1467
1.23
1537
1.31
1608
1.40
1600
985
0.64
1067
0.74
1145
0.83
1219
0.93
1290
1.03
1359
1.12
1428
1.21
1496
1.30
1565
1.39
1637
1.47
1700
1016
0.73
1099
0.82
1177
0.92
1251
1.02
1322
1.11
1391
1.21
1459
1.30
1528
1.39
1597
1.48
--
--
1800
1051
0.82
1134
0.92
1212
1.02
1286
1.11
1357
1.21
1426
1.30
1494
1.40
1562
1.49
1632
1.57
--
--
1900
1088
0.93
1171
1.02
1249
1.12
1323
1.22
1394
1.31
1463
1.41
1532
1.50
1600
1.59
--
--
--
--
2000
1128
1.04
1211
1.14
1289
1.23
1363
1.33
1434
1.43
1503
1.52
1571
1.61
1640
1.70
--
--
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Field supplied AK41 x 3/4" fixed blower pulley with Motor rated at 2.4-hp
--
Exceeds recommended blower speed
1
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
47
Johnson Controls Ducted Systems
Содержание ZQ Series
Страница 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 8: ...Nomenclature INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 8 Johnson Controls Ducted Systems ...
Страница 87: ...Start Up Sheet INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 87 Johnson Controls Ducted Systems ...
Страница 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Страница 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Страница 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Страница 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...