Table 38: Additional Static Resistance - ZQ04-06
Electric Heat kW
Model
Size Tons
CFM
1
Cooling Only
2, 3
Economizer
4 in. Filter
6/6.5
9.2/10.5/11
13.8/14/16
23
900
0.04
0.15
---
0.00
0.00
0.01
0.01
1000
0.05
0.18
---
0.00
0.00
0.02
0.02
1100
0.06
0.21
---
0.01
0.01
0.02
0.03
1200
0.07
0.24
---
0.01
0.01
0.02
0.03
1300
0.10
0.28
---
0.01
0.01
0.03
0.03
1400
0.12
0.33
---
0.02
0.02
0.03
0.04
1500
0.14
0.44
---
0.02
0.02
0.04
0.04
1600
0.16
0.52
---
0.02
0.02
0.04
0.05
1700
0.18
0.59
---
0.03
0.03
0.05
0.05
1800
0.22
0.66
---
0.03
0.03
0.05
0.06
1900
0.25
0.74
---
0.04
0.04
0.06
0.07
2000
0.28
0.81
---
0.04
0.04
0.07
0.08
2100
0.33
0.88
---
0.05
0.05
0.07
0.08
2200
0.36
0.95
---
0.06
0.06
0.08
0.09
2300
0.41
1.03
---
0.06
0.06
0.09
0.10
2400
0.45
1.10
---
0.07
0.07
0.10
0.11
04 (3.0), 05 (4.0)
2500
0.50
1.17
---
0.08
0.08
0.11
0.12
1800
0.23
0.66
---
0.03
0.03
0.05
0.06
2000
0.28
0.81
---
0.04
0.04
0.07
0.08
2200
0.32
0.95
---
0.06
0.06
0.08
0.09
ZQ
06 (5.0)
2400
0.37
1.10
---
0.07
0.07
0.10
0.11
1
Add these values to the available static resistance in the respective Blower Performance Tables.
2
Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
53
Johnson Controls Ducted Systems
Содержание ZQ Series
Страница 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 8: ...Nomenclature INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 8 Johnson Controls Ducted Systems ...
Страница 87: ...Start Up Sheet INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 87 Johnson Controls Ducted Systems ...
Страница 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Страница 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Страница 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Страница 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...