Table 9: ZQ04-06 Medium Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1
Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating
/ Pwr Exh
Si
ze
(T
on
s)
N
om
in
al
U
ni
t V
ol
ta
ge
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA
(Amps)
2, 3
Min Fuse
/ Breaker
Size (Amps)
Max Fuse
/ Breaker
Size (Amps)
FLA LRA
MCA
w/Pwr Exh (Amps)
Min Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
Max Fuse
/ Breaker
Size w/ Pwr Exh (Amps)
FLA LRA
None
-
-
-
40.4
45
60
39 182 41.9 45
60
41 185
10625 4.9
1
23.6
40.4
45
60
39 182 41.9 45
60
41 185
208-1-60 24.4
144.
2
38
2.3
7.6
1.5
11125 7.9
1
38
57
60
60
52 182 58.9 60
60
54 185
None
-
-
-
39.8
40
60
39 185 41.1 45
60
40 188
10625 6.5
1
27.1
42.6
45
60
39 185 44.3 45
60
41 188
230-1-60 24.4
144.
2
38
2.3
7
1.3
11125 10.5
1
43.8
63.5
70
70
58 185 65.1 70
70
60 188
None
-
-
-
27.5
30
40
27 137 28.6 30
40
28 140
10625 4.9
1
13.6
27.5
30
40
27 137 28.6 30
40
28 140
11125 7.9
1
21.9
33.9
35
40
31 137 35.3 40
40
32 140
208-3-60 16 110 25
2.3
5.2
1.1
11625 12
1
33.3
48.1
50
50
44 137 49.5 50
50
46 140
None
-
-
-
27.5
30
40
27 140 28.5 30
40
28 142
10625 6.5
1
15.6
27.5
30
40
27 140 28.5 30
40
28 142
11125 10.5
1
25.3
38.1
40
40
35 140 39.4 40
40
36 142
230-3-60 16 110 25
2.3
5.2
1
11625 16
1
38.5
54.6
60
60
50 140 55.9 60
60
51 142
None
-
-
-
13.7
15
20
13
67 14.2 15
20
14
69
10646
6
1
7.2
13.7
15
20
11
67 14.2 15
20
12
69
11146 11.5
1
13.8
20.5
25
25
19
67 21.1 25
25
19
69
460-3-60 7.8 52
12
1.3
2.6
0.5
11446 14
1
16.8
24.3
25
25
22
67 24.9 25
25
23
69
None
-
-
-
10.2
15
15
10
51 10.6 15
15
11
52
11458 13.8
1
13.3
19.1
20
20
18
51 19.6 20
20
18
52
06 (5)
575-3-60 5.7 38.9
9
1.1
2
0.4
12358 23
1
22.1
30.1
35
35
28
51 30.6 35
35
28
52
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
27
Johnson Controls Ducted Systems
Содержание ZQ Series
Страница 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 8: ...Nomenclature INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 8 Johnson Controls Ducted Systems ...
Страница 87: ...Start Up Sheet INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 87 Johnson Controls Ducted Systems ...
Страница 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Страница 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Страница 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Страница 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...