Table 29: ZQ04-06 Side Duct (Gas Heat)
Available External Static
0.2
0.4
0.6
0.8
1.0
Unit (Ton)
Motor Speed
CFM
WATTS
RPM
CFM
WATTS
RPM
CFM
WATTS
RPM
CFM
WATTS
RPM
CFM
WATTS
RPM
1 (LOW)
1570
372
791
1463
399
855
1358
425
918
1260
456
983
1161
481
1044
2 (MED/LOW)
1740
468
845
1638
496
903
1543
529
965
1454
553
1015
1360
578
1070
3 (MED)
1882
569
889
1786
601
947
1687
629
1002
1587
660
1053
1487
680
1105
4 (MED/HI)
2052
732
955
1967
749
999
1883
778
1049
1788
808
1099
1621
778
1130
ZQ06 (5)
5 (HI)
2227
905
1004
2138
937
1051
2038
947
1091
1869
887
1118
1662
811
1137
ZQ04-06 Bottom Duct Application (Belt Drive)
Table 30: ZQ04 (3.0 Ton) Bottom Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
792
0.14
879
0.25
968
0.37
1055
0.49
1141
0.61
1226
0.73
1308
0.84
1388
0.93
1466
1.01
1541
1.06
1000
804
0.18
893
0.29
981
0.41
1069
0.53
1155
0.66
1239
0.77
1322
0.88
1402
0.98
1480
1.05
1554
1.10
1100
819
0.23
909
0.34
997
0.46
1084
0.58
1171
0.71
1255
0.82
1337
0.93
1418
1.03
1495
1.10
1570
1.15
1200
837
0.29
926
0.40
1015
0.52
1102
0.64
1188
0.76
1273
0.88
1355
0.99
1435
1.08
1513
1.16
1588
1.21
1300
857
0.36
946
0.46
1035
0.58
1122
0.70
1208
0.83
1293
0.94
1375
1.05
1455
1.15
1533
1.22
--
--
1400
880
0.43
969
0.53
1058
0.65
1145
0.77
1231
0.90
1315
1.02
1398
1.12
1478
1.22
1556
1.29
--
--
1500
905
0.50
994
0.61
1082
0.73
1170
0.85
1256
0.97
1340
1.09
1423
1.20
1503
1.30
1581
1.37
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
--
Exceeds recommended Blower speed
1
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
Table 31: ZQ05 (4.0 Ton) Bottom Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
908
0.34
994
0.45
1072
0.55
1145
0.64
1214
0.74
1283
0.83
1352
0.92
1424
1.01
1502
1.11
1586
1.20
1300
921
0.40
1007
0.51
1085
0.61
1158
0.70
1227
0.80
1296
0.89
1365
0.98
1437
1.07
1514
1.17
1599
1.26
1400
938
0.47
1023
0.58
1101
0.68
1174
0.77
1244
0.86
1312
0.96
1382
1.05
1454
1.14
1531
1.23
1616
1.33
1500
959
0.55
1044
0.65
1122
0.75
1195
0.85
1265
0.94
1333
1.03
1403
1.12
1475
1.21
1552
1.31
1637
1.41
1600
985
0.63
1070
0.73
1148
0.83
1221
0.93
1290
1.02
1359
1.11
1428
1.20
1500
1.29
1578
1.39
--
--
1700
1015
0.71
1100
0.82
1179
0.92
1251
1.01
1321
1.11
1389
1.20
1459
1.29
1531
1.38
1608
1.48
--
--
1800
1050
0.81
1136
0.91
1214
1.01
1287
1.11
1356
1.20
1425
1.29
1494
1.39
1566
1.48
1644
1.57
--
--
1900
1091
0.91
1176
1.02
1254
1.12
1327
1.21
1397
1.31
1465
1.40
1534
1.49
1607
1.58
--
--
--
--
2000
1136
1.02
1222
1.13
1300
1.23
1372
1.32
1442
1.42
1510
1.51
1580
1.60
--
--
--
--
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Field supplied AK41 x 3/4" fixed blower pulley with Motor rated at 2.4-hp
--
Exceeds recommended blower speed
1
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
49
Johnson Controls Ducted Systems
Содержание ZQ Series
Страница 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 8: ...Nomenclature INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 8 Johnson Controls Ducted Systems ...
Страница 87: ...Start Up Sheet INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 87 Johnson Controls Ducted Systems ...
Страница 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Страница 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Страница 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Страница 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...