4-4
IM 05P01C31-01EN
4.2 How to Set Parameters
The following operating procedure describes an example of setting alarm setpoint (A1).
Operation
1.
Hold down the
PARAMETER
key for 3 seconds in the Operation Display to call up
the [
MODE
] Menu Display.
2.
Press the
Right arrow
key to display the [
SP
] Menu Display.
3.
Press the
SET/ENTER
key to display the [
SP
] Parameter Setting Display.
4.
Press the
Down arrow
key to display the [
A1
] Parameter Setting Display.
Содержание UTAdvanced UT55A
Страница 3: ......
Страница 17: ...Blank Page ...
Страница 25: ...Blank Page ...
Страница 41: ...Blank Page ...
Страница 51: ...Blank Page ...
Страница 59: ...Blank Page ...
Страница 107: ...Blank Page ...
Страница 129: ...Blank Page ...
Страница 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 241: ...Blank Page ...
Страница 315: ...Blank Page ...
Страница 369: ...Blank Page ...
Страница 411: ...Blank Page ...
Страница 463: ...Blank Page ...
Страница 473: ...Blank Page ...
Страница 475: ...Blank Page ...