11-15
IM 05P01C31-01EN
Alarm
Functions
11
11.2 Setting Number of Alarm Groups to Use
Description
Up to eight alarm groups of alarm type, alarm hysteresis, alarm (On-/Off-) delay timer,
and alarm setpoint are available.
Unused alarm parameters can be hidden and their functions can be turned off.
The initial value of parameter ALNO. is “4.”
When ALNO. = 4, for example, only the four groups of alarm type, PV velocity alarm time
setpoint, alarm hysteresis, alarm delay timer, and alarm setpoint are displayed.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
ALNO.
Number of alarm
groups
PRO
1 to 8
CTL
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
Содержание UTAdvanced UT55A
Страница 3: ......
Страница 17: ...Blank Page ...
Страница 25: ...Blank Page ...
Страница 41: ...Blank Page ...
Страница 51: ...Blank Page ...
Страница 59: ...Blank Page ...
Страница 107: ...Blank Page ...
Страница 129: ...Blank Page ...
Страница 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 241: ...Blank Page ...
Страница 315: ...Blank Page ...
Страница 369: ...Blank Page ...
Страница 411: ...Blank Page ...
Страница 463: ...Blank Page ...
Страница 473: ...Blank Page ...
Страница 475: ...Blank Page ...