viii
IM 05P01C31-01EN
Model and Suffix Codes of UT55A (for Detailed model)
[Style:S4]
Model
Suffix code
Optional
suffix
code
Description
UT55A
Digital Indicating Controller (provided with 3 DIs, and 3 DOs) (Power
supply: 100-240 V AC)
Fixed code
-NNN
Always "-NNN”
Display language (*1)
-1
English
-2
German
-3
French
-4
Spanish
Case color
0
White (Light gray)
1
Black (Light charcoal gray)
Output 1 (*2) (*3)
-A
Analog output (current/voltage pulse)
-R
Relay output (c-contact)
-U
Universal output (current/voltage pulse/relay)
-T
Triac output
-P
Position proportional output
Output 2 (*2) (*3)
A
Analog output (current/voltage pulse)
R
Relay output (c-contact)
U
Universal output (current/voltage pulse/relay)
T
Triac output
N
None
Retransmission output
/RT
Retransmission output or 15 V DC power supply
Heater break alarm (*3)
/HA
Heater break alarm
E1 terminal area (*4)
/R1
Remote (1 additional aux. analog) input and 1 additional DI
/U1
1 additional universal input (TC/RTD/DCV/mA)
/X1
5 additional DIs
/Y1
5 additional DOs
/W1
2 additional DIs and 2 additional DOs
E2 terminal area (*4)
/A2
1 additional aux. analog input and 1 additional DI
/X2
5 additional DIs
/Y2
5 additional DOs
/W2
2 additional DIs and 2 additional DOs
E3 terminal area (*4) (*5)
/CH3
RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)
/CC3
CC-Link communication
/PD3
PROFIBUS-DP communication
/DN3
DeviceNet communication
/ET3
Ethernet communication (with serial gateway function)
/X3
5 additional DIs
/Y3
5 additional DOs
/W3
2 additional DIs and 2 additional DOs
E4 terminal area (*4) (*5)
/A4
1 additional aux. analog input and 1 additional DI
/C4
RS485 communication (Max. 19.2 kbps, 2-wire/4-wire)
/L4
24 V DC loop power supply
/AC4
1 additional aux. analog input, 1 additional DI, and RS485 communication
(Max.19.2 kbps, 2-wire)
/LC4
24 V DC loop power supply and RS485 communication (Max.19.2 kbps,
2-wire)
/X4
5 additional DIs
/Y4
5 additional DOs
/W4
2 additional DIs and 2 additional DOs
Power supply
/DC
Power supply 24 V AC/DC
Additional treatment (*6)
/CT
Coating
*1: English, German, French, and Spanish can be displayed as the guide display.
*2:
For heating/cooling output, both Output 1 and Output 2 should be specified. Not available when Output 2 is “N.” For
position proportional output, specify “-P” for Output 1 and “N” for Output 2.
*3:
The /HA option can be specified only when the code for Output 1 and 2 is “-AN”, “-RN”, “-UN” or “-TN.”
*4:
Only one option is available for each terminal area of E1 to E4.
*5:
The /L4 and /LC4 options for E4 terminal area can be specified only when the E3 terminal area option is not specified
or specified any of /CH3, /X3, /Y3 or /W3.
*6:
When the /CT option is specified, the UT55A does not conform to the safety standards (UL and CSA) and CE marking.
Содержание UTAdvanced UT55A
Страница 3: ......
Страница 17: ...Blank Page ...
Страница 25: ...Blank Page ...
Страница 41: ...Blank Page ...
Страница 51: ...Blank Page ...
Страница 59: ...Blank Page ...
Страница 107: ...Blank Page ...
Страница 129: ...Blank Page ...
Страница 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...