18-39
IM 05P01C31-01EN
Parameters
18
DI Function Numbering Menu (Menu: DI.NU)
Parameter
symbol
Name
Display
level
Setting range
Initial value
SP.B0
Bit-0 of SP number
EASY
Set an I relay number of contact
input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042, DI13:
5043, DI14: 5044, DI15: 5045,
DI16: 5046
E2 -terminal area
DI21: 5057, DI22: 5058,
DI23: 5059, DI24: 5060,
DI25: 5061, DI26: 5062
E3-terminal area
DI31: 5073, DI32: 5074,
DI33: 5075, DI34: 5076,
DI35: 5077
E4-terminal area
DI41: 5089, DI42: 5090,
DI43: 5091, DI44: 5092,
DI45: 5093, DI46: 5094
OFF
SP.B1
Bit-1 of SP number
EASY
OFF
SP.B2
Bit-2 of SP number
EASY
OFF
SP.B3
Bit-3 of SP number
EASY
OFF
PN.B0
Bit-0 of PID number
STD
OFF
PN.B1
Bit-1 of PID number
STD
OFF
PN.B2
Bit-2 of PID number
STD
OFF
PN.B3
Bit-3 of PID number
STD
OFF
MP.B0
Bit-0 of manual
preset output
number
STD
OFF
MP.B1
Bit-1 of manual
preset output
number
STD
OFF
MP.B2
Bit-2 of manual
preset output
number
STD
OFF
SP.BC
Bit changing
method of SP
number
STD
0: Status switch 1
1: Status switch 2
0
PN.BC
Bit changing
method of PID
number
PRO
0: Status switch 1
1: Status switch 2
0
MP.BC
Bit changing
method of manual
preset output
number
PRO
0: Status switch 1
1: Status switch 2
0
In Cascade control, the following parameters are also displayed for secondary loop. (the LP2 lamp
is lit)
• Parameter MP.B0, MP.B1, MP.B2, MP.BC
DI1-DI3 Contact Type Setting Menu (Menu: DI.D)
Parameter
symbol
Name
Display
level
Setting range
Initial value
DI1.D
DI1 contact type
PRO
0: The assigned function is
enabled when the contact input
is closed.
1: The assigned function is
enabled when the contact input
is opened.
0
DI2.D
DI2 contact type
PRO
0
DI3.D
DI3 contact type
PRO
0
DI Setting Menu (Menu: DI.D) (E1 to E4 terminal area)
Parameter
symbol
Name
Display
level
Setting range
Initial value
DI1.D
DIn1 contact type
PRO
0: The assigned function is
enabled when the contact input
is closed.
1: The assigned function is
enabled when the contact input
is opened.
0
DI2.D
DIn2 contact type
PRO
0
DI3.D
DIn3 contact type
PRO
0
DI4.D
DIn4 contact type
PRO
0
DI5.D
DIn5 contact type
PRO
0
n: Terminal area number (1 to 4)
18.2 List of Parameters
Содержание UTAdvanced UT55A
Страница 3: ......
Страница 17: ...Blank Page ...
Страница 25: ...Blank Page ...
Страница 41: ...Blank Page ...
Страница 51: ...Blank Page ...
Страница 59: ...Blank Page ...
Страница 107: ...Blank Page ...
Страница 129: ...Blank Page ...
Страница 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 241: ...Blank Page ...
Страница 315: ...Blank Page ...
Страница 369: ...Blank Page ...
Страница 411: ...Blank Page ...
Страница 463: ...Blank Page ...
Страница 473: ...Blank Page ...
Страница 475: ...Blank Page ...