9-1
IM 05P01C31-01EN
Auxiliary Control Functions
9
9.1 Setting SP Limiter
Description
The SP high and low limits can be set to restrict the SP to the range between those limits
whether in REM (remote) or LCL (local) mode. They works to the SP of all SP groups.
In Cascade control, the SP high and low limits can be set for both Loop1 and Loop 2.
0.0
100.0(%)
Setting range
SPH
Ac
tu
al
S
P
SPL
Setting range of actual SP
Original setting range
0.0
(%)
100.0
High limit of SP
Low limit of SP
► SP group: 6.2 Setting Target Setpoint
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SPH
SP high limit
STD
0.0 to 100.0% of PV input range
(EU), (SPL<SPH)
MPV
SPL
SP low limit
STD
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
Chapter 9 Auxiliary Control Functions
Содержание UTAdvanced UT55A
Страница 3: ......
Страница 17: ...Blank Page ...
Страница 25: ...Blank Page ...
Страница 41: ...Blank Page ...
Страница 51: ...Blank Page ...
Страница 59: ...Blank Page ...
Страница 107: ...Blank Page ...
Страница 129: ...Blank Page ...
Страница 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 241: ...Blank Page ...
Страница 315: ...Blank Page ...
Страница 369: ...Blank Page ...
Страница 411: ...Blank Page ...
Страница 463: ...Blank Page ...
Страница 473: ...Blank Page ...
Страница 475: ...Blank Page ...