IM 05P01D31-11EN  page 2/12

n

 Mounting the Instrument Main Unit

Provide an instrumented panel steel sheet of 1 to 10 mm thickness.

After opening the mounting hole on the panel, follow the procedures below to install 

the controller:

1)  Insert the controller into the opening from the front of the panel so that the 

terminal board on the rear is at the far side.

2)  Set the brackets in place on the top and bottom of the controller as shown in the 

figure below, then tighten the screws of the brackets. Take care not to overtighten 

them.

 

Bracket

(top mounting hardware)

Terminal board

Bracket

(bottom mounting hardware)

Panel

Insert a screwdriver into the

brackets to tighten the screws.

Direction to insert the

controller

Appropriate

tightening torque:

0.25 N

m

Insert the controller

into the opening at

the front of the panel.

CAUTION

•  Tighten the screws with appropriate tightening torque within 0.25 

N•m. Otherwise it may cause the case deformation or the bracket 

damage.

•  Make sure that foreign materials do not enter the inside of the

  instrument through the case’s slit holes.

n

 External Dimensions and Panel Cutout Dimensions

(25)

(53) (2.09)

[(N-1)×96+92]

117 (4.61) min.

145 (5.71)

min.

+0.8

0

+0.8

0

92

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N≥5.

65 (2.56)

20  (0.79)

11

(0.43)

UT35A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket

94.6 (3.72)

91.6 (3.61)

105.2 (4.14)

Unit: mm (approx. inch)

96 (3.78)

96 (3.78)

• General mounting

• Side-by-side close mounting

Terminal cover

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.8

0

92

+0.03

0

(3.62        )

(0.98)

+0.03

0

(3.62        )

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×3.78+3.62]         )

+0.03

0

[(N-1)×48+45]

+0.6

0

65 (2.56)

48 (1.89)

11 (0.43)

UT32A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket Terminal cover

94.6 (3.72)

96 (3.78)

105.2 (4.14)

Unit: mm (approx. inch)

70 (2.76)

min.

(25)

145 (5.71)

min.

+0.6

0

45

(53) (2.09)

+0.8

0

92

• General mounting

• Side-by-side close mounting

20  (0.79)

91.6 (3.61)

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N

r

5.

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.03

0

(3.62        )

+0.02

0

(1.77         ) (0.98)

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×1.89+1.77]        )

+0.02

0

4.  Hardware Specifications

WARNING 

This instrument is for Measurement Category I (CAT.I). Do not use it 

for measurements in locations falling under Measurement Catego-

ries II, III, and IV.

Internal Wiring

Outlet

Entrance IV

Cable

III

T

I

II

Category Measurement 

category

Description

Remarks

I

CAT.I

For measurements performed on circuits not 

directly connected to MAINS.

-

II

CAT.II

For measurements performed on circuits di

-

rectly connected to the low-voltage installation.

Appliances, portable equip-

ments, etc.

III

CAT.III

For measurements performed in the building 

installation.

Distribution board, circuit 

breaker, etc.

IV

CAT.IV

For measurements performed at the source of 

the low-voltage installation.

Overhead wire, cable 

systems, etc.

n

 Input Specifications

●Universal Input (Equipped as standard)

•  Number of inputs: 1

•  Input type, instrument range, and measurement accuracy: See the table below,

Input Type

 Instrument Range

Accuracy

ºC

ºF

Thermo-

couple

K

-270.0 to 1370.0ºC -450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C 

 

±2% of instrument range ±1 digit for 

less than -200.0°C of thermocouple K 

±1% of instrument range ±1 digit for 

less than -200.0°C of thermocouple T

-270.0 to  1000.0ºC -450.0 to 2300.0ºF

-200.0 to  500.0ºC

-200.0 to 1000.0ºF

J

-200.0 to 1200.0ºC -300.0 to 2300.0ºF

T

-270.0 to 400.0ºC

-450.0 to 750.0ºF

0.0 to  400.0ºC

-200.0 to 750.0ºF

B

0.0 to 1800.0ºC

32 to 3300ºF

±0.15% of instrument range ±1 digit 

for 400°C or more

 

±5% of instrument range ±1 digit for 

less than 400°C

S

0.0 to 1700.0ºC

32 to 3100ºF

±0.15% of instrument range ±1 digit 

R

0.0 to 1700.0ºC

32 to 3100ºF

N

-200.0 to 1300.0ºC -300.0 to 2400.0ºF

±0.1% of instrument range ±1 digit

±0.25% of instrument range ±1 digit 

for less than 0°C

E

-270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C

 

±1.5% of instrument range ±1 digit for 

less than -200.0°C of thermocouple E.

L

-200.0 to 900.0ºC

-300.0 to 1600.0ºF

U

-200.0 to 400.0ºC

-300.0 to 750.0ºF

0.0 to 400.0ºC

-200.0 to 1000.0ºF

W

0.0 to 2300.0ºC

32 to 4200ºF

±0.2% of instrument range ±1 digit 

(Note 2)  

Platinel 2

0.0 to 1390.0ºC

32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit  

PR20-40

0.0 to 1900.0ºC

32 to 3400ºF

±0.5% of instrument range ±1 digit for 

800°C or more 

 

Accuracy is not guaranteed for less 

than 800°C.  

W97Re3-

W75Re25

0.0 to 2000.0ºC

32 to 3600ºF

±0.2% of instrument range ±1 digit  

RTD

JPt100

-200.0 to 500.0ºC

-300.0 to 1000.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-150.00 to  150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Pt100

-200.0 to 850.0ºC

-300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-200.0 to 500.0ºC

-300.0 to 1000.0ºF

-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Standard signal

0.400 to 2.000 V

±0.1% of instrument range ±1 digit

1.000 to 5.000 V

4.00 to 20.00 mA

DC voltage/current

0.000 to 2.000 V

0.00 to 10.00 V

0.00 to 20.00 mA

-10.00 to 20.00 mV

0.0 to 100.0 mV

The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power 

frequency at 50/60 Hz.

Note 

1:  ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range 

 

  between -100 and 200°C.

Note 2:  W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988

• Input sampling (control) period: 200 ms

• Burnout detection:

    Functions at TC, RTD, and standard signal.

    Upscale, downscale, and off can be specified.

    For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4

 

  mA or less.

• Input bias current: 0.05 µA (for TC or RTD)

• Measured current (RTD): About 0.16 mA

• Input resistance:

    TC or mV input: 1 MΩ or more

    V input: About 1 MΩ

    mA input: About 250 Ω

• Allowable signal source resistance:

    TC or mV input: 250 Ω or less

   

Effects of signal source resistance: 0.1 µV/Ω or less

    DC voltage input: 2 kΩ or less

   

Effects of signal source resistance: About 0.01%/100 Ω

•  Allowable wiring resistance:

    RTD input: Max. 150 Ω/wire  (The conductor resistance between the three wires 

 

  shall be equal.)

    Wiring resistance effect: ±0.1ºC/10 Ω

•  Allowable input voltage/current:

    TC, mV, mA and RTD input: ±10 V DC

    V input: ±20 V DC

    mA input: ±40 mA

•  Noise rejection ratio:

    Normal mode: 40 dB or more (at 50/60 Hz)

    Common mode: 120 dB or more (at 50/60 Hz) 

    For 100-240 V AC, the power frequency can be set manually. Automatic

 

  detection is also available.

    For 24 V AC/DC, the power frequency can be set manually.

•  Reference junction compensation error:

    ±1.0ºC (15 to 35ºC)

    ±1.5ºC (-10 to 15ºC and 35 to 50ºC)

•  Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD

n

 Analog Output Specifications

•  Number of outputs:

    Control output: 1

    Cooling-side control output of Heating/cooling type (Retransmission output 

 

  terminal): 1

•  Output type: Current output or voltage pulse output

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

    The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

 

  and power frequency at 50/60 Hz.

•  Voltage pulse output:

    Use: Time proportional output

    On-voltage: 12 V or more/load resistance of 600 Ω or more

    Off-voltage: 0.1 V DC or less

    Time resolution: 10 ms or 0.1% of output, whichever is larger

n

 Step Response Time Specifications

Within 1 s (63% of analog output response time when a step change of 10 to 90% of 

input span is applied)

n

 Relay Contact Output Specifications

•  Contact type and number of outputs:

    Control output: contact point 1c; 1 point

    Heating/cooling type: contact point 1a; 2 points for both heating and cooling sides

    Alarm output: contact point 1a; 3 points (common is independent)

•  Contact rating:

    Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load)

    Contact point 1a (control output): 240 V AC, 3A or 30 V DC, 3A (resistance load)

    Contact point 1a (alarm output): 240 V AC, 1A or 30 V DC, 1 A (resistance load)

•  Use: Time proportional output, alarm output, FAIL output, etc.

•  Time resolution of control output: 10 ms or 0.1% of output, whichever is larger

Note: This cannot be used for a small load of 10 mA or less.

n

 Position Proportional Output Specifications

•  Position signal input:

    Slide resistance: 100 Ω to 2.5 kΩ of total resistance

   

100% side and slide line: with disconnection detection

   

0% side: without disconnection detection

    Current input: 4 to 20 mA (with disconnection detection)

•  Sampling period: 50 ms

•  Measurement resolution: 0.1% of input span

•  Position proportional relay output:

   

UT35A: contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)

   

UT32A: contact point 1a; 2 points, 240 V AC, 3 A or 30 V DC, 3 A (resistance load)

Note: This cannot be used for a small load of 10 mA or less.

n

 

Retransmission Output Specifications

•  Number of outputs: Retransmission output; 1, shared with 15 V DC loop power 

supply or Cooling-side control output.

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

    The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

    and power frequency at 50/60 Hz.

n

 

15 V DC Loop Power Supply Specifications

(Shared with retransmission output or Cooling-side control output.)

•  Power supply: 14.5 to 18.0 V DC

•  Maximum supply current: About 21 mA (with short-circuit current limiting circuit)

n

 Contact Input Specifications

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type: No-voltage contact input or transistor contact input

•  Input contact rating: 12 V DC, 10 mA or more

    Use a contact with a minimum on-current of 1 mA or more.

•  ON/OFF detection:

    No-voltage contact input:

   

Contact resistance of 1 kΩ or less is determined as “ON” and contact

   

resistance of 50 kΩ or more as “OFF.”

    Transistor contact input:

   

Input voltage of 2 V or less is determined as “ON” and leakage current must 

   

not exceed 100 µA when “OFF.”

•  Minimum status detection hold time: Control 50 ms

•  Use: SP switch, operation mode switch, and event input

n

 Transistor Contact Output Specifications

•  Number of outputs: See the table of Model and Suffix Codes.

•  Output type: Open collector (SINK current)

•  Output contact rating: Max. 24 V DC, 50 mA

•  Output time resolution: 200 ms

n

 Heater Break Alarm Specifications

•  Number of inputs: 2

•  Number of outputs: 2 (transistor contact output)

•  Use: Measures the heater current using an external current transformer (CT) and 

generates a heater break alarm when the measured value is less than the break 

detection value.

•  Current transformer input resistance: About 9.4 Ω

•  Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be ap-

plied.)

•  Heater current setting range: OFF, 0.1 to 300.0 Arms

    Heater current measured value display range: 0.0 to 360.0 Arms

 

Note: The CT ratio can be set. CT ratio setting range: 1 to 3300

•  Recommended CT: CT from U.R.D., Ltd.

    CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms

    CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms

•  Heater current measurement period: 200 ms

•  Heater current measurement accuracy: ±5% of current transformer input range 

span ± 1digit (CT error is not included.)

•  Heater current detection resolution: Within 1/250 of current transformer input range 

span

•  Break detection On-time: Min. 0.2 second (for time proportional output)

n

 24 V DC Loop Power Supply Specifications

•  Use: Power is supplied to a 2-wire transmitter.

•  Power supply: 21.6 to 28.0 V DC

•  Rated current: 4 to 20 mA DC

•  Maximum supply current: About 30 mA (with short-circuit current limiting circuit.)

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: