If you are using two or more groups of PID parameters, use the following table to record their setting values.

Parameter

n=2

n=3

n=4

R

P

I

D

OH

OL

MR

HYS

SU.HY

HY.UP
HY.LO

DR

SU.DR

Pc

Ic

Dc

OHc

OLc

HYSc

DB

PO

SU.PO

POc

n: group number

n

 Tuning Parameter 

Menu symbol: 

 

(TUNE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SC)

Super function

OFF: Disable

1: Overshoot suppressing function 

(normal mode)

2: Hunting suppressing function 

(stable mode)

 

Enables to answer the wider 

characteristic changes compared 

with response mode.

3: Hunting suppressing function 

(response mode)

 

Enables quick follow-up and short 

converging time of PV for the 

changed SP.

4: Overshoot suppressing function 

(strong suppressing mode)

 

Note: Setpoints 2 and 3 must be 

used in PID control or PI control. 

Disabled in the following controls:

 

1) ON/OFF control, 2) PD control, 

3) P control, 4) Heating/cooling 

control. 

Do not use the function for the 

control processes with response 

such as flow or pressure control.

OFF

EASY

(AT.TY)

Auto-tuning type

0: Normal

 

1: Stability

0

STD

(AR)

Anti-reset windup 

(excess integration 

prevention)

AUTO, 50.0 to 200.0%

AUTO

(OPR)

Output velocity limiter

OFF: Disable

 

0.1 to 100.0%/s

OFF

(MPON)

Manual preset output 

number selection

Select the output used in MAN mode 

when switched from AUTO to MAN 

mode.

OFF: Hold the control output in AUTO          

mode (bumpless)

1: Use manual preset output 1 (output 

bump)

2: Use manual preset output 2 (output 

bump)

3: Use manual preset output 3 (output 

bump)

4: Use manual preset output 4 (output 

bump)

5: Use manual preset output 5 (output 

bump)

OFF

 to

(MPO1 to MPO5)

Manual preset output 1 

to 5

-5.0 to 105.0% 

 

However, output is limited to the 

output high limit and low limit.

0.0%

Table 

below

Use the following table to record the manual preset output setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

MPOn

n

 Zone Control Parameter

Menu symbol: 

 (ZONE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to

(RP1 to RP3)

Reference point 1 to 3

Set reference points at which switch

-

ing is carried out between groups of 

PID constants according to the given 

temperature zone.

 

0.0 to 100.0% of PV input range (EU) 

 

(RP1 ≤ RP2 ≤ RP3)

100.0% 

of PV 

input 

range

Table 

below

STD

(RHY)

Zone PID switching 

hysteresis

Hysteresis can be set for switching at 

a reference point. 

0.0 to 10.0% of PV input range span 

(EUS)

0.5 % 

of PV 

input 

range 

span

(RDV)

Reference deviation

Set a deviation from SP. The PID for 

reference deviation is used if there 

is a larger deviation than the preset 

reference deviation.

 

OFF: Disable

 

0.0 + 1 digit to 100.0% of PV input 

range span (EUS)

OFF

For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID se-

lection.

Use the following table to record the reference point setting value.

Parameter

n=1

n=2

n=3

RPn

n

 P Parameter (for Ladder Program) 

Menu symbol: 

 (PPAR)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(P01 to P10)

P01 to P10 parameter

-19999 to 30000 (Set a decimal point 

position using LL50A Parameter Set-

ting Software.)

0

Table 

below

STD

Parameter

n=01

n=02

n=03

n=04

n=05

n=06

n=07

n=08

n=09

n=10

Pn

Setup Parameters

Hold down the PARAMETER key or PARA key and Left arrow key simultaneously for 3 

seconds to move from the Operation Display or Operation Parameter Setting Display to 

the Setup Parameter Setting Display.

Press the DISPLAY key or DISP key once to return to the Operation Display.

Menu

DISPLAY key

or DISP key

SET/ENTER key

PARAMETER key

or PARA key

key

key

key

key

key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

Parameter Setting 

Display are changed 

in a circular pattern.

Move to the Operation Parameter Setting Display: 

          Hold down the PARAMETER key or PARA key for 3 sec.

Hold down PARAMETER key or PARA key and 

Left arrow key simultaneously for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the Model 

and Suffix codes, control type (CNT), etc.

n

 Control Function Setting Parameter

Menu symbol: 

 (CTL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(CNT)

Control type

PID: PID control

ONOF: ON/OFF control (1 point of 

hysteresis)

ONOF2: ON/OFF control (2 points of 

hysteresis)

2P2L: Two-position two-level control

H/C: Heating/cooling control

PID

EASY

(SPGR.)

Number of SP groups

Set a number of SP groups to use.

1 to 4

4

STD

(ZON)

Zone PID selection

If set to “SP group number selection,” 

allows PID constants to be selected 

for each SP group.

 

If set to “Zone PID selection,” 

automatically selects PID constants 

according to the range set in the 

Reference point. 

0: SP group number selection 1

1: 

Zone PID selection (selection by PV)

2: Zone PID selection (selection by 

target SP)

3: SP group number selection 2

4: 

Zone PID selection (selection by SP) 

0

(PIDG.)

Number of PID groups

Set a number of PID groups to use. 

 

1 to 4

4

n

 PV Input Setting Parameter 

Menu symbol: 

 (PV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(IN)

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.0 to 150.0 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20 : 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

OFF

EASY

(UNIT)

PV input unit

-: No unit, C: Degree Celsius

 

-: No unit, - -: No unit, - - -: No unit, 

F: Degree Fahrenheit

C

(RH)

Maximum value of PV 

input range

Depends on the input type.

- For temperature input -

Set the temperature range that is 

actually controlled. (RL<RH)

- For voltage / current input -

Set the range of a voltage / current 

signal that is applied.

The scale across which the voltage/

current signal is actually controlled 

should be set using the maximum 

value of input scale (SH) and mini-

mum value of input scale (SL).

(Input is always 0% when RL = RH.)

Depends 

on the 

input type

(RL)

Minimum value of PV 

input range

Depends 

on the 

input type

(SDP)

PV input scale decimal 

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(SH)

Maximum value of PV 

input scale

-19999 to 30000, (SL<SH),

| SH - SL | ≤ 30000

Depends 

on the 

input type

(SL)

Minimum value of PV 

input scale

Depends 

on the 

input type

(BSL)

PV input burnout action

OFF: Disable

UP: Upscale

DOWN: Downscale

Depends 

on the 

input type

STD

W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25

n

 Input Range, SP Limiter Setting Parameter

Menu symbol: 

 (MPV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P.UNI)

Control PV input unit

-: No unit

C: Degree Celsius

-: No unit

- -: No unit

- - -: No unit

F: Degree Fahrenheit

Same 

as PV 

input 

unit

STD

(P.DP)

Control PV input decimal

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

1

(P.RH)

Maximum value of

control PV input range

-19999 to 30000, (P.RL<P.RH),

| P.RH - P.RL | ≤ 30000

Depends 

on the 

input type

(P.RL)

Minimum value of control

PV input range

Depends 

on the 

input type

(SPH)

SP high limit

0.0 to 100.0% of PV input range (EU), 

(SPL<SPH)

100.0 % 

of PV 

input 

range

(SPL)

SP low limit

0.0 % 

of PV 

input 

range

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: