IM 05P01D31-11EN  page 6/12

■  Parameters to be set

Control Type

Parameter Symbol Name of Parameter

Setting Range

CNT

Control type

PID: PID control

ONOF: ON/OFF control (1 point of hysteresis)

ONOF2: ON/OFF control (2 points of hysteresis)

2P2L: Two-position two-level control

H/C: Heating/cooling controll

Note:  Some setpoints may not be displayed depending on the model and suffix codes.

Input Function

Parameter Symbol Name of Parameter

Setting Range

IN

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20: 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

UNIT

PV input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit

RH

Maximum value of 

PV input range

Depends on the input type.

- For temperature input -

Set the temperature range that is actually controlled. 

(RL<RH)

- For voltage / current input -

Set the range of a voltage / current signal that is applied.

The scale across which the voltage / current signal is 

actually controlled should be set using the maximum value 

of input scale (SH) and minimum value of input scale (SL).

(Input is always 0% when RL = RH.)

RL

Minimum value of 

PV input range

SDP

PV input scale 

decimal point 

position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

SH

Maximum value of 

PV input scale

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

SL

Minimum value of 

PV input scale

Note 1: SDP, SH, and SL are displayed only for voltage/current input.

Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988

Output Function

Parameter Symbol Name of Parameter

Setting Range

OT

Output type selection

Upper two digits

Lower two digits

Control output or Heating-

side control output (Lower 

two digits)

00: OFF

01: OUT terminals 

      (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals

 

      (voltage pulse)

08: RET/OUT2 terminals

 

      (current)

Cooling-side control output 

(Upper two digits)

00: OFF

01: OUT terminals 

      (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals

 

      (voltage pulse)

08: RET/OUT2 terminals

 

      (current)

CT

Control output cycle 

time

Heating-side control 

output cycle time 

(in Heating/cooling 

control)

0.5 to 1000.0 s

CTc

Cooling-side control 

output cycle time 

(in Heating/cooling 

control)

4.  Adjusting Valve Position Automatically 

 

(for a Position Proportional Type Controller Only)

The following operating procedure describes how to input feedback signals from the 

control valve and adjust the fully-open and fully-closed positions of the control valve 

automatically. The fully-open and fully-closed positions of the valve can be adjusted 

automatically by inputting feedback signals from the valve. To adjust the valve posi-

tion, you need to carry out the connection and bring the controller into manual mode. 

For the connection, see “6. Terminal Wiring Diagrams” in "Installation and Wiring", 

and for the manual mode, see “5. Switching between AUTO and MAN” in "Opera-

tions."

CTL menu is displayed.

Press the Right arrow key until OUT menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Up arrow key.

Hold down the keys for 3 seconds.

Show the Operation Display.

OUT menu is displayed.

OFF blinks.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

7.

MAN

is lit

* When a password is set, PASS is displayed. 

   If the correct password is not entered, setup 

   parameters cannot be changed. 

The parameter V.AT (automatic valve 

position adjustment) is displayed.

ON is displayed.

Blinks during the change. 

 When the adjustment is completed normally, the indication 

  automatically returns to OFF.

●  

When VAT.E appears on PV display, it indicates an error.

    Check the wiring for feedback input and perform the 

automatic adjustment again. To perform a valve adjustment 

manually, see User’s Manual.

ON has been registered and the automatic 

adjustment of the valve position starts.

V.AT blinks during the automatic adjustment. 

After the adjustment is completed, press 

the DISPLAY key or DISP key once to return 

to the Operation Display.

5.  Setting Alarm Type

The following operating procedure shows an example of changing the alarm-1 type 

(factory default: PV high limit alarm) to PV low limit alarm.

MODE menu is displayed.

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

Energized/De-energized

Latch action

Stand-by action

The alarm-1 type setpoint 02 (PV low limit)

is registered.

After the setup is completed, press the DISPLAY key 

or DISP key once to return to the Operation Display.

Symbol

● 

To change the alarm type, change the last 2 digits of the 

   5-digit value.

● 

Stand-by action and excitation are turned on or off by 

   selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual.

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and 

the Left/Right arrow keys to move between digits. 

MODE menu is displayed.

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

Press the SET/ENTER key.

1.

2.

3.

4.

5.

6.

Energized/De-energized

Latch action

Stand-by action

The alarm-1 type setpoint 02 (PV low limit)

is registered.

After the setup is completed, press the DISPLAY key 

or DISP key once to return to the Operation Display.

Symbol

● 

To change the alarm type, change the last 2 digits of the 

   5-digit value.

● 

Stand-by action and excitation are turned on or off by 

   selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual.

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and 

the Left/Right arrow keys to move between digits. 

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open

(

unlit

)

Closed

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Cooling-side control output 

high limit (17)

Control output low limit (16)

Cooling-side control output 

low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open

(

unlit

)

Open

(

unlit

)

Open

(

lit

)

Closed

(lit)

Open

(

unlit

)

Open

(

lit

)

Closed

(unlit)

Closed

(unlit)

Open

(

lit

)

Closed

(unlit)

Closed

(unlit)

Open

(

lit

)

Open

(

lit

)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Open

(

unlit

)

Open

(

unlit

)

Open

(

unlit

)

Open

(

unlit

)

Open

(

unlit

)

Open

(un

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See

User’s

 Manual.

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open

(

unlit

)

Closed

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Cooling-side control output 

high limit (17)

Control output low limit (16)

Cooling-side control output 

low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open

(

unlit

)

Open

(

unlit

)

Open

(

lit

)

Closed

(lit)

Open

(

unlit

)

Open

(

lit

)

Closed

(unlit)

Closed

(unlit)

Open

(

lit

)

Closed

(unlit)

Closed

(unlit)

Open

(

lit

)

Open

(

lit

)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Closed

(lit)

Open

(

unlit

)

Open

(

unlit

)

Open

(

unlit

)

Open

(

unlit

)

Open

(

unlit

)

Open

(un

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Open

(

lit

)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Closed

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See

User’s

 Manual.

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

6.   Setting Alarm Setpoint

The following operating procedure shows an example of setting the alarm-1 setpoint 

of group 1 to 180.0.

Before setting the alarm setpoint, check the alarm type.

To change the alarm type, see “5. Setting Alarm Type.” 

Press the Right arrow key.

Press the SET/ENTER key.

SP menu is displayed.

Display the parameter and group 

that need to be changed.

Blinks during the change. 

The setpoint has been registered.

After the setup is completed, press 

the DISPLAY key or DISP key once

to return to the Operation Display. 

Press the SET/ENTER key.

Press the Down arrow key until A1 appears.

Press the SET/ENTER key.

Show the Operation Display.
Display MODE menu with the same procedure as described in 

Setting Alarm Type.

1.
2.

3.

4.

5.

6.

Group

The parameter A1 is displayed.

A1 to A4 represent the alarm-1 to -4 setpoints.

Each parameter and group can be changed 

in the Parameter Setting Displays of alarms

using arrow keys.

Up/Down arrow keys: parameters

Left/Right arrow keys: groups

Change the setpoint using the Up/Down arrow 

keys to increase and decrease the value and 

the Left/Right arrow keys to move between digits.

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: