background image

IM 05P01D31-11EN  page 5/12

Contents

1.   Names and Functions of Display Parts

2.   Setup Procedure

3.   Quick Setting Function (Setting of Input and Output)

4.  

Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)

5.   Setting Alarm Type

6.   Setting Alarm Setpoint

1.  Names and Functions of Display Parts

(2) + (3) + (4) : Setpoint display

(1)

(2)

(9)

(10)

(11)

(4)

(8)

(10)

(9)

(3)
(5)
(6)

(7)

(8)

(2)

(3)

(4)
(5)
(6)

(11)

No. in figure

Name

Description

(1)

PV display 

 

(white or red)

Displays PV.

Displays an error code if an error occurs.

Displays the scrolling guide in the Menu Display and Parameter 

Setting Display when the guide display ON/OFF is set to ON.

(2)

Group display (green)

Displays a group number (1 to 4 or R) and terminal area (E1 to E4).

1 to 4 represent SP numbers in the Operation Display.

R and E1 to E4 are displayed in the Parameter Setting Display.

(3)

Symbol display (orange) Displays a parameter symbol.

(4)

Data display (orange) Displays a parameter setpoint and menu symbol.

(5)

Bar-graph display 

(orange)

Displays control output value (OUT) and measured input value (PV).

The data to be displayed can be set by the parameter.

Initial value: Deviation, Heating-side control output (in Heating/

cooling control)

(6)

Event indicator 

 

(orange)

Lit when the alarms 1 to 4 occur.

Event displays other than alarms can be set by the parameter.

(7)

Key navigation indica-

tor (green)

Lit or blinks when the Up/Down or Left/Right arrow key operation 

is possible.

(8)

Parameter display level 

indicator (green)

Displays the setting conditions of the parameter display level func-

tion.

Parameter display level

EASY

PRO

Easy setting mode

Lit

Unlit

Standard setting mode

Unlit

Unlit

Professional setting mode

Unlit

Lit

(9)

Status indicator 

(green and red)

Displays the operating conditions and control status.

Indicator

Description 

REM

Lit when in remote mode (REM).

STOP

Lit when in stop mode (STOP).

MAN

Lit when in manual mode (MAN). 

Blinks during auto-tuning.

(10)

Security indicator (red) Lit if a password is set. The setup parameter settings are locked.

(11)

Ladder operation 

indicator (green)

Lit while the ladder operation is executed.

(4)

(5)
(6)

(1)
(2)

(3)

(4)

(5)

(6)

(1)

(2)

No. in figure

Name

Description

(1)

UT35A: DISPLAY key

UT32A: DISP key

Used to switch the Operation Displays.

Press the key in the Operation Display to switch the provided 

Operation Displays.

Press the key in the Menu Display or Parameter Setting Display 

to return to the Operation Display.

(2)

UT35A: 

PARAMETER key

UT32A: PARA key

Hold down the key for 3 seconds to move to the Operation 

Parameter Setting Display.

Hold down the key and the Left arrow key simultaneously for 3 

seconds to move to the Setup Parameter Setting Display.

Press the key in the Parameter Setting Display to return to the 

Menu Display. Press the key once to cancel the parameter set-

ting (setpoint is blinking).

(3)

SET/ENTER key

Up/Down/Left/Right 

arrow keys

SET/ENTER key

  Press the key in the Menu Display to move to the Parameter 

  Setting Display of the Menu. Press the key in the Parameter 

  Setting Display to transfer to the parameter setting mode 

  (setpoint is blinking), and the parameter can be changed.

  Press the key during parameter setting mode to register the 

  setpoint.

Up/Down/Left/Right arrow keys

  Press the Left/Right arrow keys in the Menu Display to switch 

  the Displays.

  Press the Up/Down/Left/Right arrow keys in the Parameter 

  Setting Display to switch the Displays.

  Press the Up/Down arrow keys during parameter setting mode

  (setpoint is blinking) to change a setpoint.

  Press the Left/Right arrow keys during parameter setting mode

  

(setpoint is blinking) to move between digits according to the parameter.

(4)

Light-loader interface

It is the communication interface for the adapter cable used when 

setting and storing parameters from a PC. The LL50A Parameter 

Setting Software (sold separately) is required.

(5)

A/M key

Used to switch between AUTO and MAN modes.

The setting is switched between AUTO and MAN each time the 

key is pressed.

(6)

User function keys

The UT35A has F1, F2, and Fn keys.

The UT32A has only the Fn key. The user can assign a function 

to the key. The function is set by the parameter. 

Note:  The communication connector (maintenance port) for LL50A Parameter Setting Software is 

on the top of the unit. 

2.  Setup Procedure

The following flowchart shows the setup procedure for UT35A/UT32A. 

Install and wire a controller.

Monitoring and control of regular operations

Adjust PID using auto-tuning or manually for PID control.

Other setup

Operation

NO

NO

NO

YES

YES

YES

Set the other parameters as needed.

PID tuning

Input setup

Output setup

Installation

and wiring

Power ON

Control type setup

Control type setup

Input/output setup

Valve position

adjustment

Use

Quick setting

function?

Position

proportional

type?

Position

proportional

type?

For Position proportional type

3.  Quick Setting Function (Setting of Input and Output)

The Quick setting function is a function to easily set the basic function of the control-

ler.

Turn on the controller to start the Quick setting function.

This function allows you to easily set the control type, input, and output, and quickly 

start the control action.

The items (parameters) to be set by Quick setting function are as follows.

(1) Control type (PID control, Heating/cooling control, etc.)

(2) Input function (PV input type, range, scale (at voltage input), etc.)

(3) Output function (control output type and cycle time)

After turning on the controller, first decide whether or not to use the Quick setting func-

tion.

Operation in Initial Display

·  Press the SET/ENTER key while YES is displayed to start the Quick setting function.

·  If you change YES to NO and press the SET/ENTER key, Operation Display will 

appear without starting the Quick setting function.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

Operation

Guide

Initial Settings

UT35A/UT32A

Digital Indicating Controllers

Operation Guide

This operation guide describes basic settings and operations of the UT35A/UT32A.

For details of each function, see the electronic manual.

The scrolling guide is displayed on PV display in the Parameter Setting Display.

This guide can be turned on/off with the Fn key. 

·  To change and set the parameter setting, press the SET/ENTER key to start the 

setpoint blinking. The blinking state allows you to make changes (setting mode). 

Use the Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/EN-

TER key to register the setting.

  Making Settings Using Quick Setting Function

Example:  Setting  to  PID  control,  thermocouple  type  K  (range  of  0.0  to 

500.0

0

C), and current control output

For the detailed procedure and switching of displays, see "Flow of Quick Setting 

Function" below. For the parameters to set, see the next page. 

(1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.

(2) Set the control type parameter (CNT) to PID (PID control).

(3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0 

0

C). 

(4) Set the PV input unit parameter (UNIT) to C (Degree Celsius).

(5) Set the maximum value of PV input range parameter (RH) to 500.0.

(6) Set the minimum value of PV input range parameter (RL) to 0.0.

(7) Set the output type selection parameter (OT) to OUT terminals (current=00.02).

(8) Finally, EXIT is displayed. Change NO to YES and press the SET/ENTER key to 

complete the setup. Operation Display appears. 

Press the SET/ENTER key while YES 

is displayed to start the Quick setting.

[

NO

]

Select NO with the Down 

arrow key and press the 

SET/ENTER key.

Select NO to return to

 the Operation Display.

Power-on

First, the control type 

parameter (CNT) 

is displayed.

Initial value: PID (PID control)

Press the Down arrow key.

The PV input type 

parameter (IN) is 

displayed.

Initial value: OFF

Press the SET/ENTER key.

OFF blinks.

Blinking allows you to 

change the setting.

Press the Up arrow key.

K1 is displayed.

K1 has been registered.

Press the SET/ENTER key.

Press the Down arrow key.

[YES]

1.

2.

3.

4.

5.

6.

Quick setting starts

■  Flow of Quick Setting Function

In Quick setting mode, the parameter guide appears on PV display.

This guide can be turned on/off with the Fn key.

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) 

has been changed to 500.0.

The setpoint for the parameter RH has been registered.

Press the Down arrow key.

Operation Display

8.

9.

10.

11.

12.

The PV input unit parameter (UNIT) is displayed.

Initial value: C (Degree Celsius)

7.

Press the Down arrow key.

Follow the same procedure to set RL 

to 0.0 and OT to 00.02.

Set other parameters as needed.

Displays the measured 

input value (PV).

Displays the target 

setpoint (SP).

Finally, EXIT is displayed.

Press the SET/ENTER key to swtich to the setting mode.

Change NO to YES and press the SET/ENTER key 

to complete the setup of the basic function.

Operation Display appears.

The Quick setting function continues in the NO state. 

The upper limit value of the setting range is displayed 

for the parameter RH (maximum value of PV input range). 

Press the SET/ENTER key.

Press the SET/ENTER key.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and the Left/Right arrow 

keys to move between digits.

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: