background image

IM 05P01D31-11EN   page 12/12

■ Key Lock Setting Parameter 

Menu symbol: 

 (KLOC)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(COM.W)

Communication write 

enable/disable

OFF: Enable, ON: Disable

OFF

STD

(DATA)

Front panel parameter 

data (▼,▲) key lock

OFF: Unlock, ON: Lock

OFF

(A/M)

Front panel A/M key lock

OFF

■ DI Function Registration Parameter

Menu symbol: 

 (DI.SL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(A/M)

AUTO/MAN switch

Set an I relay number of contact 

input.

Set “OFF” to disable the function.

Standard terminals

DI1: 5025, DI2: 5026

E1-terminal area

 

DI11: 5041, DI12: 5042, DI13: 5043, 

DI14: 5044, DI15: 5045

5025

STD

(R/L)

REMOTE/LOCAL switch

OFF

(S/R)

STOP/RUN switch 

5026

(AUTO)

Switch to AUTO

OFF

(MAN)

Switch to MAN

OFF

(REM)

Switch to REMOTE

OFF

(LCL)

Switch to LOCAL

OFF

(AT)

Auto-tuning START/STOP 

switch

OFF

(LAT)

Latch release

OFF

(LCD)

LCD backlight ON/OFF 

switch

OFF

■ DI Function Numbering Parameter

Menu symbol: 

 (DI.NU)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SP.B0)

Bit-0 of SP number

Set an I relay number of contact input.

 

Set “OFF” to disable the function.

 

Standard terminals 

DI1: 5025, DI2: 5026

E1-terminal area

 

DI11: 5041, DI12: 5042, DI13: 5043, 

DI14: 5044, DI15: 5045

OFF

EASY

(SP.B1)

Bit-1 of SP number

OFF

(SP.B2)

Bit-2 of SP number

OFF

(PN.B0)

Bit-0 of PID number

OFF

STD

(PN.B1)

Bit-1 of PID number

OFF

(PN.B2)

Bit-2 of PID number

OFF

(MP.B0)

Bit-0 of manual preset 

output number

OFF

(MP.B1)

Bit-1 of manual preset 

output number

OFF

(MP.B2)

Bit-2 of manual preset 

output number

OFF

■ AL1-AL3 Function Registration Parameter

Menu symbol: 

 (ALM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(AL1.S)

AL1 function selection

Set an I relay number. For the items 

other than below, see User's Manual.

Ex.) Set the number 4353 for AL1.S 

to use the alarm 1.

Set “OFF” to disable the function.

No function: OFF

Alarm 1: 4353

Alarm 2: 4354

Alarm 3: 4355

Alarm 4: 4357

AUTO (ON ) / MAN (OFF) status: 4193

REM (ON) / LCL (OFF) status: 4194

STOP (ON) / RUN (OFF) status: 4195

FAIL (Normally ON) output: 4256

4353

STD

(AL2.S)

AL2 function selection

4354

(AL3.S)

AL3 function selection

4355

(OR.S)

OUT relay function 

selection 

OFF

(OR2.S)

OUT2 relay function 

selection

OFF

■ DO Setting Parameter (E1/E4-terminal Area)

Menu symbol: 

 (DO)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(DO1.S)

DO11/DO41 function 

selection

Same as AL1.S

Set “OFF” to disable the function

OFF

Table 

below

STD

(DO2.S)

DO12/DO42 function 

selection

OFF

(DO3.S)

DO43 function selection

OFF

(DO4.S)

DO44 function selection

OFF

(DO5.S)

DO45 function selection

OFF

Use the following table to record DO setting value.

Parameter

E1-terminal Area

E4-terminal Area

DO1.S
DO2.S
DO3.S
DO4.S
DO5.S

■ System Setting Parameter

Menu symbol: 

 (SYS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(R.MD)

Restart mode

Set how the controller should recover 

from a power failure of 5 seconds or 

more.

CONT: Continue action set before 

power failure.

MAN: Start from MAN.

AUTO: Start from AUTO.

CONT

STD

(R.TM)

Restart timer

Set time between power on and the 

instant where controller starts compu

-

tation. 

0 to 10 s

0

(EPO)

Input error preset output

Set preset output value when the 

input burnout or ADC error occurs. 

Manual output is prioritized when the 

input burnout occurs in MAN.

0: Preset output

 

1: 0% output

 

2: 100% output

0

(FREQ)

Power frequency

AUTO, 60: 60 Hz, 50: 50 Hz

AUTO

EASY

(QSM)

Quick setting mode

OFF: Disable

 

ON: Enable

ON

(LANG)

Guide display language

ENG: English

FRA: French

GER: German

SPA: Spanish

Depe-

nds on 

the 

model 

and 

suffix 

codes

(PASS)

Password setting

0 (No password) to 65535

 

Setting “0” means “without password 

protection.”  

0

■ Error and Version Confirmation Parameter (for display only)

Menu symbol: 

 (VER)

Parameter 

symbol

Name of Parameter

Status record

Display 

level

(PA.ER)

Parameter error status

EASY

(OP.ER)

Option error status

(AD1.E)

A/D converter error status 1 

(AD2.E)

A/D converter error status 2 

(PV1.E)

PV input error status

(LA.ER)

Ladder error status 

(MCU)

MCU version

(DCU)

DCU version

(ECU1)

ECU-1 version (E1-terminal area)

(ECU3)

ECU-3 version (E3-terminal area)

(ECU4)

ECU-4 version (E4-terminal area)

(PARA)

Parameter version

(H.VER)

Product version

(

SER1

)

Serial number 1

(SER2)

Serial number 2 

(MAC1)

MAC address 1 (E3-terminal area)

(MAC2)

MAC address 2 (E3-terminal area)

(MAC3)

MAC address 3 (E3-terminal area)

■ Parameter Display Level Parameter

Menu symbol: 

 (LVL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(LEVL)

Parameter display level

EASY: Easy setting mode

STD: Standard setting mode

PRO: Professional setting mode

STD

EASY

* For Professional setting mode, see User’s Manual.

Trademarks

● Our product names or brand names mentioned in this manual are 

  the trademarks or registered trademarks of Yokogawa Electric Corporation.

● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks

  of Adobe Systems Incorporated.

● Ethernet is a registered trademark of XEROX Corporation in the United States.

● Modbus is a registered trademark of Schneider Electric.

● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.

● CC-Link is a registered trademark of CC-Link Partner Association.

● We do not use the TM or ® mark to indicate these trademarks or 

  registered trademarks in this manual.

● All other product names mentioned in this manual are trademarks

  or registered trademarks of their respective companies.

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: