IM 05P01D31-11EN page 9/12
Operation Parameters
Hold down the PARAMETER key or PARA key for 3 seconds to move from the Opera-
tion Display to the Operation Parameter Setting Display. Press the DISPLAY key or
DISP key once to return to the Operation Display.
Menu
Hold down PARAMETER key or PARA key
for 3 sec.
DISPLAY key
or DISP key
SET/ENTER key
PARAMETER key
or PARA key
key
key
key
key
key
The parameter groups can be switched using , keys.
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
Parameter
END
Menu
END
Menu
END
END
Menu Display and
Parameter Setting
Display are changed
in a circular pattern.
Move to the Setup Parameter Setting Display:
Hold down the PARAMETER key or PARA key and the Left arrow key simultaneously
for 3 sec.
Operation for Setting
· To select the parameter setting displayed as the initial value, press the Down arrow
key to move to the next parameter.
· To change and set the parameter setting, press the SET/ENTER key to start the set-
point blinking. The blinking state allows you to make changes (setting mode). Use the
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to
register the setting.
Note that there are some parameters which are not displayed depending on the model
and suffix codes, control type (CNT), etc.
n
Operation Mode
Menu symbol:
(MODE)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(S.R)
STOP/RUN switch
STOP: Stop mode
RUN: Run mode
Preset output (PO) is generated in
STOP mode.
Default: Not displayed. STOP/RUN
switch is assigned to contact input.
RUN
EASY
(R.L)
REMOTEL/LOCAL
switch
LCL: Local mode
REM: Remote mode
(Displayed only in cases where the
communication is specified.)
LCL
(AT)
AUTO-tuning switch
OFF: Disable
1 to 4: Perform auto-tuning. Tuning
result is stored in the specified num-
bered PID.
R: Tuning result is stored in the PID
for reference deviation.
OFF
(SPNO.)
SP number selection
1 to 4 (Depends on the setup param-
eter SPGR. setting.)
1
(PID)
PID number
The PID group number being selected
is displayed.
1 to 4, R: PID group for reference
deviation
1
n
SELECT Parameter
Menu symbol:
(CS)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
Registered
parameter
symbol
SELECT parameter 10
to 19
Setting range of a registered param-
eter.
For details, see User's Manual.
0
Table
below
EASY
Parameter
n=10
n=11
n=12
n=13
n=14
n=15
n=16
n=17
n=18
n=19
CSn
For the registration of SELECT parameters, see User's Manual.
n
SP and Alarm Setpoint Setting Parameter
Menu symbol:
(SP)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(SP)
Target setpoint
0.0 to 100.0% of PV input range (EU)
(Setting range: SPL to SPH)
SPL
Table
below
EASY
(SUB)
Sub-target setpoint (in
Two-position two-level
control)
Set the offset from SP.
-100.0 to 100.0% of PV input range
span (EUS)
0.0 %
of PV
input
range
span
(PIDN)
PID number selection
Set a PID group number to use.
1 to 4 (Depends on the setup param-
eter PIDG. setting.)
1 to 4
to
(A1 to A4)
Alarm-1 to -4 setpoint
Set a display value of setpoint of PV
alarm, SP alarm, deviation alarm,
output alarm, or velocity alarm.
-19999 to 30000 (Set a value within the
input range.)
Decimal point position depends on the
input type
0
For the parameter SP (target setpoint), 4 groups are displayed for the factory default.
The number of groups can be changed by the setup parameter SPGR. (number of
SP groups). For the alarm setpoint parameter, alarm-1 to -4 are displayed for the fac-
tory default. The number of alarms can be changed using the setup parameter ALNO.
(number of alarms). To change the number of SP groups or alarms, see User's Manual.
Use the following table to record SP and alarm setpoints.
Parameter
n=1
n=2
n=3
n=4
SP
SUB
PIDN
A1
A2
A3
A4
n: group number
n
SP-related Setting Parameter
Menu symbol:
(SPS)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(RT)
Remote input ratio
SP = Remote input x RT + Remote
input bias
0.001 to 9.999
1.000
STD
(RBS)
Remote input bias
-100.0 to 100.0% of PV input range
span (EUS)
0.0 %
of PV
input
range
span
(UPR)
SP ramp-up rate
Used to prevent SP from changing
suddenly.
Set a ramp-up rate or ramp-down rate
per hour or minute. Set a time unit
using the parameter TMU.
OFF, 0.0 + 1 digit to 100.0% of PV
input range span (EUS)
OFF
EASY
(DNR)
SP ramp-down rate
OFF
(TMU)
SP ramp-rate time unit
HOUR: Ramp-up rate or ramp-down
rate per hour
MIN: Ramp-up rate or ramp-down
rate per minute
HOUR
(SPT)
SP tracking selection
Tracking is performed when the mode
changes from Remote to Local. (The
local setpoint keeps track of the
remote setpoint.)
OFF, ON
ON
STD
(PVT)
PV tracking selection
Causes the setpoint to keep track of
the PV so the setpoint automatically
reverts to its original value at a preset
rate of change. The UPR, DNR, and
TMU are used in combination. Oper-
ating conditions: 1) MAN → AUTO, 2)
STOP → AUTO, 3) Power-on, 4) SP
number change, 5) SP change
OFF, ON
OFF
n
Alarm Function Setting Parameter
Menu symbol:
(ALRM)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(AL1 to AL4)
Alarm-1 to 4 type
Example: Alarm-1
Stand-by
action
Latch action
Energized/
De-energize
Alarm
type
Set a 5-digit value in the following
order.
[Alarm type: 2 digits (see below)] +
[Without (0) or With (1) Stand-by ac-
tion] + [Energized (0) or De-energized
(1)] + [Latch action (0/1/2/3/4)]
For latch action, see User's Manual.
AL1,
AL3:
PV high
limit (01)
Without-
Stand-
by
action
(0)
Energi-
zed (0)
Latch
action
(0)
AL2,
AL4:
PV low
limit (02)
Without
Stand-
by
action
(0)
Energi-
zed (0)
Latch
action
(0)
Table
below
EASY
Alarm type: 2 digits
00: Disable
01: PV high limit
02: PV low limit
03: SP high limit
04: SP low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
09: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13:
Target SP deviation high and low limits
14: Target SP deviation within high
and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
to
(VT1 to VT4)
PV velocity alarm time
setpoint 1 to 4
0.01 to 99.59 (minute.second)
1.00
to
(HY1 to HY4)
Alarm-1 to -4 hysteresis
Set a display value of setpoint of
hysteresis.
-19999 to 30000 (Set a value within
the input range.)
Decimal point position depends on
the input type.
10
to
(DYN1 to DYN4)
Alarm-1 to -4 On-delay
timer
An alarm output is ON when the delay
timer expires after the alarm setpoint
is reached.
0.00 to 99.59 (minute.second)
0.00
STD
(AMD)
Alarm mode
0: Always active
1: Not active in STOP mode
2: Not active in STOP or MAN mode
0
For the alarm function setting parameter, 4 alarms are displayed for the factory default.
The number of alarms can be changed by the setup parameter ALNO. (number of
alarms). To change the number of alarms, see User's Manual.
Parameter
n=1
n=2
n=3
n=4
ALn
VTn
HYn
DYNn
n: alarm number
n
PV-related Setting Parameter
Menu symbol:
(PVS)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(BS)
PV input bias
-100.0 to 100.0% of PV input range
span (EUS)
0.0 %
of PV
input
range
span
EASY
(FL)
PV input filter
OFF, 1 to 120 s
OFF
n
PID Setting Parameter
Menu symbol:
(PID)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(P)
Proportional band
Heating-side proportion-
al band (in Heating/cool-
ing control)
0.0 to 999.9%
When 0.0% is set, it operates as
0.1%.
Heating-side ON/OFF control applies
when 0.0% in Heating/cooling control
5.0%
EASY
(I)
Integral time
Heating-side integral time
(in Heating/cooling control)
OFF: Disable
1 to 6000 s
240 s
(D)
Derivative time
Heating-side derivative time
(in Heating/cooling control)
OFF: Disable
1 to 6000 s
60 s
(OH)
Control output high limit
Heating-side control
output high limit (in
Heating/cooling control)
-4.9 to 105.0%, (OL<OH)
In Heating/cooling control: 0.1 to
105.0% (OL<OH)
100.0%
(OL)
Control output low limit
Heating-side control
output low limit (in Heat-
ing/cooling control)
-5.0 to 104.9%, (OL<OH), SD: Tight
shut
In Heating/cooling control: 0.0 to
104.9% (OL<OH)
0.0%
(MR)
Manual reset
Enabled when integral time is OFF.
The manual reset value equals the
output value when PV = SP.
-5.0 to 105.0%
50.0%
(HYS)
Hysteresis (in ON/OFF
control, Position
proportional control, or
Two-position two-level
control)
Heating-side ON/OFF
control hysteresis (in
Heating/cooling control)
In ON/OFF control or Two-position
two-level control: 0.0 to 100.0% of
PV input range span (EUS)
In Heating/cooling control or Position
proportional control: 0.0 to 100.0%
In
ON/OFF
control
or
Two-
position
two-level
control:
0.5 % of
PV input
range
span
In Heat
-
ing/
cooling
control
or
Position
proportional
control:
0.5 %
(SU.HY)
Sub-hysteresis (in
Two-position two-level
control)
0.0 to 100.0% of PV input range
span (EUS)
0.5 %
of PV
input
range
span
(HY.UP)
Upper-side hysteresis
(in ON/OFF control)
0.5 %
of PV
input
range
span
(HY.LO)
Lower-side hysteresis
(in ON/OFF control)
0.5 %
of PV
input
range
span
(DR)
Direct/reverse action
switch
RVS: Reverse action
DIR: Direct action
RVS
STD
(SU.DR)
Sub-direct/reverse
action switch (in Two-
position two-level
control)
DIR
(Pc)
Cooling-side propor-
tional band
0.0 to 999.9%
(Cooling-side ON/OFF control
applies when 0.0% in Heating/cool-
ing control)
5.0%
EASY
(Ic)
Cooling-side integral
time
OFF: Disable
1 to 6000 s
240 s
(Dc)
Cooling-side derivative
time
OFF: Disable
1 to 6000 s
60 s
(OHc)
Cooling-side control
output high limit
0.1 to 105.0%, (OLc<OHc)
100.0%
(OLc)
Cooling-side control
output low limit
0.0 to 104.9%, (OLc<OHc)
0.0%
(HYSc)
Cooling-side ON/OFF
control hysteresis
0.0 to 100.0%
0.5%
(DB)
Output dead band (in
Heating/cooling control
or Position proportional
control)
In Heating/cooling control: -100.0 to
50.0%
In Position proportional control: 1.0
to 10.0%
3.0%
(PO)
Preset output
Heating-side preset
output (in Heating/cool-
ing control)
In STOP mode, fixed control output
can be generated. In Position propor-
tional control, Valve opening can be
set; -5.0 to 105.0%
0.0%
(SU.PO)
Sub-preset output (in
Two-position two-level
control)
In STOP mode, fixed sub-control
output can be generated.
0%, 100%
0%
(POc)
Cooling-side preset
output
In STOP mode, cooling-side fixed
control output can be generated.
-5.0 to 105.0%
0.0%
For the PID setting parameter, 4 groups are displayed for the factory default.
The number of groups can be changed by the setup parameter PIDG. (number of PID
groups). To change the number of PID groups, see User's Manual.
Operation
Guide
UT35A/UT32A
Digital Indicating Controllers
Operation Guide
This operation guide describes the functions of parameters briefly. The parameter
symbols listed are in the order shown on the display in each group of menu symbols.
In addition, each parameter table has a “User Setting” column, where you can record
your setpoints when setting them in the controller. The scrolling guide is displayed on
PV display in the Parameter Setting Display. This guide can be turned on/off with
the Fn key.
Yokogawa Electric Corporation
Parameters