IM 05P01D31-11EN   page 9/12

Operation Parameters

Hold down the PARAMETER key or PARA key for 3 seconds to move from the Opera-

tion Display to the Operation Parameter Setting Display. Press the DISPLAY key or 

DISP key once to return to the Operation Display.

Menu

Hold down PARAMETER key or PARA key

for 3 sec.

DISPLAY key

or DISP key

SET/ENTER key

PARAMETER key

or PARA key

key

key

key

key

key

The parameter groups can be switched using     ,      keys.

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

Parameter Setting 

Display are changed 

in a circular pattern.

Move to the Setup Parameter Setting Display: 

     Hold down the PARAMETER key or PARA key and the Left arrow key simultaneously 

     for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the model 

and suffix codes, control type (CNT), etc.

n

 Operation Mode

Menu symbol: 

 

(MODE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(S.R)

STOP/RUN switch

STOP: Stop mode 

RUN: Run mode

 

Preset output (PO) is generated in 

STOP mode. 

Default: Not displayed. STOP/RUN 

switch is assigned to contact input.

RUN

EASY

(R.L)

REMOTEL/LOCAL 

switch

LCL: Local mode

 

REM: Remote mode

(Displayed only in cases where the 

communication is specified.)

LCL

(AT)

AUTO-tuning switch

OFF: Disable

 

1 to 4: Perform auto-tuning. Tuning 

result is stored in the specified num-

bered PID.

 

R: Tuning result is stored in the PID 

for reference deviation.

OFF

(SPNO.)

SP number selection

1 to 4 (Depends on the setup param-

eter SPGR. setting.)

1

(PID)

PID number

The PID group number being selected 

is displayed. 

1 to 4, R: PID group for reference 

deviation

1

n

 SELECT Parameter

Menu symbol: 

 (CS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

Registered 

parameter 

symbol

SELECT parameter 10 

to 19

Setting range of a registered param-

eter.

For details, see User's Manual.

0

Table 

below

EASY

Parameter 

n=10

n=11

n=12

n=13

n=14

n=15

n=16

n=17

n=18

n=19

CSn

For the registration of SELECT parameters, see User's Manual.

n

 SP and Alarm Setpoint Setting Parameter

Menu symbol: 

 (SP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SP)

Target setpoint

0.0 to 100.0% of PV input range (EU) 

(Setting range: SPL to SPH)

SPL

Table 

below

EASY

(SUB)

Sub-target setpoint (in 

Two-position two-level 

control)

Set the offset from SP. 

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

(PIDN)

PID number selection

Set a PID group number to use.

 

1 to 4 (Depends on the setup param-

eter PIDG. setting.)

1 to 4

 to 

(A1 to A4)

Alarm-1 to -4 setpoint

Set a display value of setpoint of PV 

alarm, SP alarm, deviation alarm, 

output alarm, or velocity alarm.

 

-19999 to 30000 (Set a value within the 

input range.)

 

Decimal point position depends on the 

input type

0

For the parameter SP (target setpoint), 4 groups are displayed for the factory default. 

The number of groups can be changed by the setup parameter SPGR. (number of 

SP groups). For the alarm setpoint parameter, alarm-1 to -4 are displayed for the fac-

tory default. The number of alarms can be changed using the setup parameter ALNO. 

(number of alarms). To change the number of SP groups or alarms, see User's Manual.

Use the following table to record SP and alarm setpoints.

Parameter

n=1

n=2

n=3

n=4

SP

SUB

PIDN

A1
A2
A3
A4

n: group number

n

 SP-related Setting Parameter 

Menu symbol: 

 (SPS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(RT)

Remote input ratio

SP = Remote input x RT + Remote 

input bias

 

0.001 to 9.999

1.000

STD

(RBS)

Remote input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

(UPR)

SP ramp-up rate

Used to prevent SP from changing 

suddenly. 

Set a ramp-up rate or ramp-down rate 

per hour or minute. Set a time unit 

using the parameter TMU.

 

OFF, 0.0 + 1 digit to 100.0% of PV 

input range span (EUS)

OFF

EASY

(DNR)

SP ramp-down rate

OFF

(TMU)

SP ramp-rate time unit

HOUR: Ramp-up rate or ramp-down 

rate per hour 

MIN: Ramp-up rate or ramp-down 

rate per minute

HOUR

(SPT)

SP tracking selection

Tracking is performed when the mode 

changes from Remote to Local. (The 

local setpoint keeps track of the 

remote setpoint.)

OFF, ON

ON

STD

(PVT)

PV tracking selection

Causes the setpoint to keep track of 

the PV so the setpoint automatically 

reverts to its original value at a preset 

rate of change. The UPR, DNR, and 

TMU are used in combination. Oper-

ating conditions: 1) MAN → AUTO, 2) 

STOP → AUTO, 3) Power-on, 4) SP 

number change, 5) SP change

OFF, ON

OFF

 

n

 Alarm Function Setting Parameter

Menu symbol: 

 (ALRM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(AL1 to AL4)

Alarm-1 to 4 type

Example: Alarm-1

Stand-by

action

Latch action

Energized/

De-energize

Alarm

type

Set a 5-digit value in the following 

order.

[Alarm type: 2 digits (see below)] + 

[Without (0) or With (1) Stand-by ac-

tion] + [Energized (0) or De-energized 

(1)] + [Latch action (0/1/2/3/4)]

For latch action, see User's Manual. 

AL1, 

 

AL3: 

 

PV high 

limit (01)

 

Without-

Stand-

by 

action 

(0)

 

Energi-

zed (0) 

Latch 

action 

(0) 

AL2, 

AL4: 

PV low 

limit (02) 

Without 

Stand-

by 

action 

(0)

Energi-

zed (0) 

Latch 

action 

(0)

Table 

below

EASY

Alarm type: 2 digits

00: Disable

01: PV high limit

02: PV low limit

03: SP high limit

04: SP low limit

05: Deviation high limit

06: Deviation low limit

07: Deviation high and low limits

08: Deviation within high and low limits

09: Target SP high limit

10: Target SP low limit

11: Target SP deviation high limit

12: Target SP deviation low limit

13: 

Target SP deviation high and low limits

14: Target SP deviation within high 

and low limits

15: OUT high limit

16: OUT low limit

17: Cooling-side OUT high limit

18: Cooling-side OUT low limit

19: Analog input PV high limit

20: Analog input PV low limit

27: Feedback input high limit

28: Feedback input low limit

29: PV velocity

30: Fault diagnosis

31: FAIL

 to 

(VT1 to VT4)

PV velocity alarm time 

setpoint 1 to 4

0.01 to 99.59 (minute.second)

1.00

 to 

(HY1 to HY4)

Alarm-1 to -4 hysteresis

Set a display value of setpoint of 

hysteresis. 

-19999 to 30000 (Set a value within 

the input range.)

 

Decimal point position depends on 

the input type.

10

 to 

(DYN1 to DYN4)

Alarm-1 to -4 On-delay 

timer

An alarm output is ON when the delay 

timer expires after the alarm setpoint 

is reached. 

0.00 to 99.59 (minute.second)

0.00

STD

(AMD)

Alarm mode

0: Always active

1: Not active in STOP mode

2: Not active in STOP or MAN mode

0

For the alarm function setting parameter, 4 alarms are displayed for the factory default. 

The number of alarms can be changed by the setup parameter ALNO. (number of 

alarms). To change the number of alarms, see User's Manual.

Parameter

n=1

n=2

n=3

n=4

ALn
VTn

HYn

DYNn

n: alarm number

n

 PV-related Setting Parameter 

Menu symbol: 

 (PVS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BS)

PV input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % 

of PV 

input 

range 

span

EASY

(FL)

PV input filter

OFF, 1 to 120 s

OFF

 

n

 PID Setting Parameter

Menu symbol: 

 (PID)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P)

Proportional band

 

Heating-side proportion-

al band (in Heating/cool-

ing control)

0.0 to 999.9%

 

When 0.0% is set, it operates as 

0.1%.

 

Heating-side ON/OFF control applies 

when 0.0% in Heating/cooling control

5.0%

EASY

(I)

Integral time

 

Heating-side integral time 

(in Heating/cooling control)

OFF: Disable

 

1 to 6000 s

240 s

(D)

Derivative time

 

Heating-side derivative time 

(in Heating/cooling control)

OFF: Disable

 

1 to 6000 s

60 s

(OH)

Control output high limit

 

Heating-side control 

output high limit (in 

Heating/cooling control)

-4.9 to 105.0%, (OL<OH)

 

In Heating/cooling control: 0.1 to 

105.0% (OL<OH)

100.0%

(OL)

Control output low limit

 

Heating-side control 

output low limit (in Heat-

ing/cooling control)

-5.0 to 104.9%, (OL<OH), SD: Tight 

shut 

In Heating/cooling control: 0.0 to 

104.9% (OL<OH)

0.0%

(MR)

Manual reset

Enabled when integral time is OFF.

 

The manual reset value equals the 

output value when PV = SP.

 

-5.0 to 105.0%

50.0%

(HYS)

Hysteresis (in ON/OFF 

control, Position 

proportional control, or 

Two-position two-level 

control)

 

Heating-side ON/OFF 

control hysteresis (in 

Heating/cooling control)

In ON/OFF control or Two-position 

two-level control: 0.0 to 100.0% of 

PV input range span (EUS)

 

In Heating/cooling control or Position 

proportional control: 0.0 to 100.0%

In 

ON/OFF 

control 

or 

Two-

position 

two-level 

control: 

0.5 % of 

PV input 

range 

span 

In Heat

-

ing/

cooling 

control

or

Position

proportional

control: 

0.5 %

(SU.HY)

Sub-hysteresis (in 

Two-position two-level 

control)

0.0 to 100.0% of PV input range 

span (EUS)

0.5 % 

of PV 

input 

range 

span

(HY.UP)

Upper-side hysteresis 

(in ON/OFF control)

0.5 % 

of PV 

input 

range 

span

(HY.LO)

Lower-side hysteresis 

(in ON/OFF control)

0.5 % 

of PV 

input 

range 

span

(DR)

Direct/reverse action 

switch

RVS: Reverse action

DIR: Direct action

RVS

STD

(SU.DR)

Sub-direct/reverse 

action switch (in Two-

position two-level 

control)

DIR

(Pc)

Cooling-side propor-

tional band

0.0 to 999.9%

 

(Cooling-side ON/OFF control 

 

applies when 0.0% in Heating/cool-

ing control)

5.0%

EASY

(Ic)

Cooling-side integral 

time

OFF: Disable

 

1 to 6000 s

240 s

(Dc)

Cooling-side derivative 

time

OFF: Disable

 

1 to 6000 s

60 s

(OHc)

Cooling-side control 

output high limit

0.1 to 105.0%, (OLc<OHc) 

100.0%

(OLc)

Cooling-side control 

output low limit

0.0 to 104.9%, (OLc<OHc) 

0.0%

(HYSc)

Cooling-side ON/OFF 

control hysteresis

0.0 to 100.0%

0.5%

(DB)

Output dead band (in 

Heating/cooling control 

or Position proportional 

control)

In Heating/cooling control: -100.0 to 

50.0% 

 

In Position proportional control: 1.0 

to 10.0%

3.0%

(PO)

Preset output 

Heating-side preset 

output (in Heating/cool-

ing control)

In STOP mode, fixed control output 

can be generated. In Position propor-

tional control, Valve opening can be 

set; -5.0 to 105.0%

0.0%

(SU.PO)

Sub-preset output (in 

Two-position two-level 

control)

In STOP mode, fixed sub-control 

output can be generated.

 

0%, 100%

0%

(POc)

Cooling-side preset 

output

In STOP mode, cooling-side fixed 

control output can be generated.

 

-5.0 to 105.0%

0.0%

For the PID setting parameter, 4 groups are displayed for the factory default. 

The number of groups can be changed by the setup parameter PIDG. (number of PID 

groups). To change the number of PID groups, see User's Manual.

Operation

Guide

UT35A/UT32A

Digital Indicating Controllers

Operation Guide

This operation guide describes the functions of parameters briefly. The parameter 

symbols listed are in the order shown on the display in each group of menu symbols. 

In addition, each parameter table has a “User Setting” column, where you can record 

your setpoints when setting them in the controller. The scrolling guide is displayed on 

PV display in the Parameter Setting Display. This guide can be turned on/off with 

the Fn key.

Yokogawa Electric Corporation

Parameters

Содержание UTAdvanced UT35A

Страница 1: ... CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Note The last digit of the display language code x0 has been changed into the case color code n UT32A Style S1 Model Suffix code Optional suffix code Description UT32A Digital Indicating Controller provided with retrans mission output or 15 V DC loop power supply 2 DIs and 3 DOs Power supply 100 24...

Страница 2: ...nput bias current 0 05 µA for TC or RTD Measured current RTD About 0 16 mA Input resistance TC or mV input 1 MΩ or more V input About 1 MΩ mA input About 250 Ω Allowable signal source resistance TC or mV input 250 Ω or less Effects of signal source resistance 0 1 µV Ω or less DC voltage input 2 kΩ or less Effects of signal source resistance About 0 01 100 Ω Allowable wiring resistance RTD input Ma...

Страница 3: ...e taken do not install the primary and secondary power cables close to each other If there is a risk of external lightning surges use a lightning arrester etc For TC input use shielded compensating lead wires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a ...

Страница 4: ...rol output is relay Can be used for 15 V DC loop power supply when not used for retransmission output PV RET Equipped as standard Contact input Contact rating 12 V DC 10 mA or more External contact input DI2 DI1 COM AUTO when DI1 ON MAN when DI1 OFF STOP when DI2 ON RUN when DI2 OFF Common DI2 DI1 COM 5V 5V No voltage contact Transistor contact UT UT 210 211 212 210 211 212 Function can be assigne...

Страница 5: ... Set the other parameters as needed PID tuning Input setup Output setup Installation and wiring Power ON Control type setup Control type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to eas...

Страница 6: ... of changing the alarm 1 type factory default PV high limit alarm to PV low limit alarm MODE menu is displayed Press the Right arrow key until ALRM menu appears Press the SET ENTER key Press the SET ENTER key Hold down the key for 3 seconds Show the Operation Display ALRM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Ene...

Страница 7: ...hange The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the paramete...

Страница 8: ...ion parameter error Operation parameter data is corrupted Initialized to user default value SLOT 0015 0015 Error occurs to all hardware of E1 to E4 terminal areas Setup parameter OP ER Nonresponding hardware of extended function E1 to E4 terminal areas Inconsistence of system data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal ...

Страница 9: ...atch action 0 AL2 AL4 PV low limit 02 Without Stand by action 0 Energi zed 0 Latch action 0 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high...

Страница 10: ...oint blinking The blinking state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters which are not displayed depending on the Model and Suffix codes control type CNT etc n Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting R...

Страница 11: ... NONE None EVEN Even ODD Odd EVEN STP Stop bit 1 1 bit 2 2 bits 1 DLN Data length 7 7 bits 8 8 bits 8 ADR Address 1 to 99 1 Ethernet Communication Setting Parameter E3 terminal Area Menu symbol ETHR Parameter symbol Name of Parameter Setting Range Initial value User setting Display level HSR High speed response mode OFF 1 to 8 1 EASY BPS Baud rate 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 3840...

Страница 12: ...45 function selection OFF Use the following table to record DO setting value Parameter E1 terminal Area E4 terminal Area DO1 S DO2 S DO3 S DO4 S DO5 S System Setting Parameter Menu symbol SYS Parameter symbol Name of Parameter Setting Range Initial value User setting Display level R MD Restart mode Set how the controller should recover from a power failure of 5 seconds or more CONT Continue action...

Отзывы: