15-30
IM 05P07A01-01EN
15.4 Reading via Communication
When reading the alarm status
Read I relay numbers 4321 to 4336 for Loop-1 alarm-1 to alarm-8 status.
I relay No.
Symbol
Event
4321 to 4336
ALM1_L1~ALM8_L1
Loop-1 alarm-1 to alarm-8 status (Same as D2011) *
4337 to 4352
ALM1_L2~ALM8_L2
Loop-2 alarm-1 to alarm-8 status (Same as D2013)
•
•
•
•
•
•
4545 to 4576
*: The contents of Loop-1 alarm-1 to alarm-8 status (I relay numbers 4321 to 4336:
ALM1_L1 to ALM8_L1) are the same as the bit configuration of D register number
D2011 (Loop-1 alarm-1 to alarm-8 status). Refer to the bit configuration of D2011
described in “Chapter 14 Functions and Applications of D Registers (for UT75A).”
The following shows the bit configuration of D2011 described in “Chapter 14 Functions
and Applications of D Registers (for UT75A).”
Bit Configuration of D2011: ALM_L1 (Loop-1 alarm-1 to alarm-8 status)
Bit
Symbol
Event
0
ALM1_L1
‘1’ when Loop-1 alarm 1 is ON; ‘0’ when OFF
1
ALM2_L1
‘1’ when Loop-1 alarm 2 is ON; ‘0’ when OFF
2
ALM3_L1
‘1’ when Loop-1 alarm 3 is ON; ‘0’ when OFF
3
4
ALM4_L1
‘1’ when Loop-1 alarm 4 is ON; ‘0’ when OFF
5
ALM5_L1
‘1’ when Loop-1 alarm 5 is ON; ‘0’ when OFF
6
ALM6_L1
‘1’ when Loop-1 alarm 6 is ON; ‘0’ when OFF
7
8
ALM7_L1
‘1’ when Loop-1 alarm 7 is ON; ‘0’ when OFF
9
ALM8_L1
‘1’ when Loop-1 alarm 7 is ON; ‘0’ when OFF
10 to 15
Note
When specifying an I relay number for communication, begin the number with the character “I.”
Example: Set “I4321” to specify the ALM1_L1 (I relay No.: 4321).
Содержание UTAdvanced Series
Страница 17: ...Blank Page...
Страница 77: ...Blank Page...
Страница 285: ...Blank Page...
Страница 325: ...Blank Page...
Страница 467: ...Blank Page...
Страница 557: ...Blank Page...
Страница 825: ...Blank Page...
Страница 861: ...Blank Page...
Страница 863: ...Blank Page...
Страница 865: ...Blank Page...