6-84
IM 05P07A01-01EN
6.4 UT55A/UT52A/UP55A D Registers
Register
No.
Description
Range and meaning of value
D5015
D5016
SEG.T
Segment setting method
0: TIME (Segment time setting)
1: TM.RT (Segment ramp-rate setting)
* Note: A change of setting deletes a program
pattern.
D5017
TMU
Program time unit
0: HH.MM (hour.minute)
1: MM.SS (minute.second)
D5018
PT2.G
Program pattern-2 retransmission
0: OFF (Not used)
1: ON (used)
* The controller can serve as a program pattern
generator.
* Retransmission output types (RTS, O1RS, or
O2RS) need to be set to SP2.
D5019
SMP
Input sampling period (control period)
0: 50 (50 ms) *
1: 100 (100 ms)
2: 200 (200 ms)
*: For UT55A/UT52A only
D5020 to D5100