6-131
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Reading Pattern Data (D8001 to D8100)
Modbus communication
The example for the communication command is Modbus/RTU. For easy understanding,
space is added but it is not present in the actual command. The device address is “1.”
Reading start segment data
Example: Reading start target setpoint (SSP_L1) for pattern 2
(1) Write pattern number “2” to D8001 (PTNO._C), and segment number “0” to D8002
(SEGNO._C).
(2) Read from D8003 (SSP_L1).
(3) Read from D8042 (PTN.ERR).
If reading PTN.ERR results in other than zero, an error occurred. If zero, the read
was successful.
(1) 01 10 1F40 0002 04 0002 0000 [CRC]
(2) 01 03 1F42 0001 [CRC]
(3) 01 03 1F69 0001 [CRC]
Example: Batch reading start segment data for pattern 2
(1) Write pattern number “2” to D8001 (PTNO._C), and segment number “0” to D8002
(SEGNO._C).
(2) Read from 40 registers continuously: D8003 (SSP_L1) to D8041 (P.NAME) and
D8042 (PTN.ERR).
If reading PTN.ERR results in other than zero, an error occurred. If zero, the read
was successful.
(1) 01 10 1F40 0002 04 0002 0000 [CRC]
(2) 01 03 1F42 0028 [CRC]
PC link communication
The example for the communication command is a PC link without a checksum. The
device address is “1.”
Reading start segment data
Example: Reading start target setpoint (SSP_L1) for pattern 2
(1) Write pattern number “2” to D8001 (PTNO._C), and segment number “0” to D8002
(SEGNO._C).
(2) Read from D8003 (SSP_L1).
(3) Read from D8042 (PTN.ERR).
If reading PTN.ERR results in other than zero, an error occurred. If zero, the read
was successful.
(1) 01010WWRD8001,02,00020000
(2) 01010WRDD8003,01
(3) 01010WRDD8042,01
Example: Batch reading start segment data for pattern 2
(1) Write pattern number “2” to D8001 (PTNO._C), and segment number “0” to D8002
(SEGNO._C).
(2) Read from 40 registers continuously: D8003 (SSP_L1) to D8041 (P.NAME) and
D8042 (PTN.ERR).
If reading PTN.ERR results in other than zero, an error occurred. If zero, the read
was successful.
(1) 01010WWRD8001,02,00020000
(2) 01010WRDD8003,40
Содержание UTAdvanced Series
Страница 17: ...Blank Page...
Страница 77: ...Blank Page...
Страница 285: ...Blank Page...
Страница 325: ...Blank Page...
Страница 467: ...Blank Page...
Страница 557: ...Blank Page...
Страница 825: ...Blank Page...
Страница 861: ...Blank Page...
Страница 863: ...Blank Page...
Страница 865: ...Blank Page...