12-39
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A-L)
12
12.4 UT35A-L D Registers
System Setting (D6401 to D6500)
Register
No.
Description
Range and meaning of value
D6401 to D6408
D6403
R.MD
Restart mode
0: Limit output is ON at power on in any cases
1: Limit output is OFF at power on when PV doesn't
exceed SP
D6409
C.GRN
Response as GREEN Series
0: OFF (Works as UT35A-L in communication of device
information response or broadcasting.)
1: ON (Works as GREEN Series in communication of
device information response or broadcasting.)
D6410
FREQ
Power frequency
0: AUTO
1: 60 Hz
2: 50 Hz
D6411 to D6416
D6417
QSM
Quick setting mode
0: OFF (Disable)
1: ON (Enable)
D6418 to D6420
D6421
U.DEF
Initialization to user default value
1
2345: Initialization, automatically returned to "0" after
initialization.
D6422
D6423
F.DEF
Initialization to factory default value
-
12345: Initialization, automatically returned to "0" after
initialization. *
D6424 to D6430
D6431
LEVL
Parameter display level
1: EASY (Easy setting mode)
2: STD (Standard setting mode)
3: PRO (Professional setting mode)
D6432 to D6500
Free Area (D6501 to D7000)
Register
No.
Description
Range and meaning of value
D6501 to D7600
Free area
Содержание UTAdvanced Series
Страница 17: ...Blank Page...
Страница 77: ...Blank Page...
Страница 285: ...Blank Page...
Страница 325: ...Blank Page...
Страница 467: ...Blank Page...
Страница 557: ...Blank Page...
Страница 825: ...Blank Page...
Страница 861: ...Blank Page...
Страница 863: ...Blank Page...
Страница 865: ...Blank Page...